TROUBLESHOOTING
SYMPTOM | POSSIBLE CAUSE | CORRECTIVE ACTION | |
Engine does not crank | Loose battery cables | • Check all battery cable connections |
|
| Defective battery | • Test battery. Replace as necessary. |
|
|
| • Check battery charger inline fuse |
|
| Improper battery charger function | • Ensure charger is plugged into GFCI | |
|
| receptacle |
|
|
| • Check for tripped GFCI receptacle. Reset if | |
|
| required. |
|
|
| • Check for tripped breaker in branch circuit | |
|
| supplying GFCI. Reset if required. |
|
|
| • Check all charger cable connections for | |
|
| cleanness and tightness. |
|
|
| • Check charger lights to verify correct | |
|
| operation. See Table A, Page 29. |
|
| Fault in starter signal circuit | • Contact a qualified generator dealer for service | |
|
| assistance. |
|
| Blown control circuit fuse | • Check control circuit fuse. | |
Engine cranks without starting | Low battery | • Test battery. Replace as necessary. |
|
|
| • Ensure charger is plugged into GFCI | |
|
| receptacle |
|
|
| • Check for tripped GFCI receptacle. Reset if | |
|
| required. |
|
|
| • Check for tripped breaker in branch circuit | |
|
| supplying GFCI. Reset if required. |
|
|
| • Check all charger cable connections for | |
|
| cleanness and tightness. |
|
|
| • Check charger lights to verify correct | |
|
| operation. See Table A, Page 29. |
|
| Poor fuel supply | • Ensure all manual shutoff valves are open |
|
|
| • Check for proper fuel supply pressure |
|
|
| • Verify size and fill level of propane tank (LPG | |
|
| only) |
|
|
| • Check fuel solenoid voltage during cranking | |
Engine starts then | Low oil pressure | • Check engine oil level |
|
immediately shuts down |
| • Check switch for proper function |
|
| High engine temperature | • Allow engine to cool, then restart |
|
|
| • Decrease loads on generator |
|
|
| • Check enclosure openings for blockage |
|
|
| • Check oil cooler for blockage | |
No generator output | Main line circuit breaker tripped | • Check breaker. Clear faults, then reclose | |
|
| breaker. |
|
| Disconnect breaker tripped | • Check for tripped breaker in circuit between | |
|
| generator output and transfer switch. Clear | |
|
| fault, then reclose breaker. |
|
| Generator loss of excitation | • Contact a qualified generator dealer for service | |
|
| assistance. |
|
| Excitation capacitor failure | • Contact a qualified generator dealer for service | |
|
| assistance. |
|
| Generator diode or varistor failure | • Contact a qualified generator dealer for service | |
|
| assistance. |
|
| Generator head fault | • Contact a qualified generator dealer for service | |
|
| assistance. | |
|
|
|
|