Powermate PM400911 owner manual Gfci Circuit Supply, Generator Start Signal, ATS1, ATS2

Models: PM400911

1 48
Download 48 pages 59.39 Kb
Page 11
Image 11
GFCI CIRCUIT SUPPLY

GFCI CIRCUIT SUPPLY

A ground fault circuit interrupting (GFCI) receptacle is provided with the generator to power the battery charger for reliable starting. It is also intended to power an optional block heater if that option is desired. Connection of this circuit to a power supply that is only present when normal utility power is supplied is recommended. By connecting the GFCI in this fashion, it is possible to insure that neither the battery charger or block heater are on while the engine is running. Precautions are engineered into the generator to prevent these occurances but connection of the circuit in this fashion provides an additional fail-safe method of engine and battery protection.

Input to the GFCI circuit is 3-wire, 120V, 15A. Connections include a "hot" lead (L1), neutral (N) and ground lead. Positions of the incoming wire connections are labeled at the auxiliary connection block, shown in Fig.C. Select proper GFCI supply wire size according to allowable ampacities given in Table 310-16 of the latest revision of The National Electric Code(NFPA 70). To connect the wires, strip the insulation back approximately ¼" from the end of the wire, insert the stripped end under the screw and washer on the terminal block, then torque the terminal block screw to 20 in-lbs (2.3 N-m).

FIG. C

GFCI

CIRCUIT

GENERATOR START SIGNAL NEUTRAL SUPPLY

 

(CONNECT TO

L1

120V UTILITY

 

 

POWER)

GENERATOR START SIGNAL

When the control panel mode switch is placed in the AUTO position, generator starting and stopping is controlled by the opening or closing of a set of voltage free contacts. Two wires from those contacts are connected to the generator through the auxiliary connection block shown in Fig. D. Use of a twisted pair of stranded copper wire no smaller than AWG 18 gage is recommended. To insure proper operation of the auto start feature, use a transfer switch offering “close-to-run control contacts. To connect the wires, strip the insulation back approximately ¼" from the end of the wire, insert the stripped end under the screw and washer on the terminal block, then torque the terminal block screw to 20 in-lbs (2.3 N-m).

FIG. D

 

GENERATOR

 

START SIGNAL

ATS1

(CONNECT TO

 

AUTOMATIC

ATS2

TRANSFER

 

SWITCH)

200-2341

11

Page 11
Image 11
Powermate PM400911 owner manual Gfci Circuit Supply, Generator Start Signal, ATS1, ATS2