Powermate PM400911 Troubleshooting, Symptom, Low generator output voltage, Possible Cause

Models: PM400911

1 48
Download 48 pages 59.39 Kb
Page 35
Image 35
Low generator output voltage

TROUBLESHOOTING

SYMPTOM

Low generator output voltage

Overspeed light stays lit

Underspeed light stays lit

Overcrank light stays lit Not In Auto light stays lit

Low oil pressure light stays lit

Low battery light stays lit

High engine temperature light stays lit

 

POSSIBLE CAUSE

 

CORRECTIVE ACTION

 

Low engine speed

 

• Verify correct engine speed. Remove excess

 

 

 

loads or adjust speed as required.

 

Excitation capacitor failure

 

• Contact a qualified generator dealer for service

 

 

 

assistance.

 

Generator diode or varistor failure

 

• Contact a qualified generator dealer for service

 

 

 

assistance.

 

Shutdown due to high engine

 

• Verify correct engine speed setting. Adjust

 

speed

 

engine speed as required.

 

Shutdown due to low engine

 

• Reduce loads connected to generator

 

speed

 

 

 

 

 

• Check engine speed setting at no load.

 

 

 

Adjust as required.

 

Failure to start

 

• See "Engine cranks without starting"

 

Generator not set for unattended

 

• Place mode switch into AUTO position if

 

 

 

operation

 

automatic function is required

 

Shutdown due to low engine oil

 

• Check engine oil level.

 

pressure

 

 

 

 

 

• Verify correct type of engine oil for ambient

 

 

 

temperature conditions

 

Low battery

 

• Test battery. Replace as necessary.

 

 

 

• Ensure charger is plugged into GFCI

 

 

 

receptacle

 

 

 

• Check for tripped GFCI receptacle. Reset if

 

 

 

required.

 

 

 

• Check for tripped breaker in branch circuit

 

 

 

supplying GFCI. Reset if required.

 

 

 

• Check all charger cable connections for

 

 

 

cleanness and tightness.

 

 

 

• Check battery charger inline fuse

 

 

 

• Check charger lights to verify correct

 

 

 

operation. See Table A, Page 29.

 

Blown charger circuit fuse

 

• Check engine alternator fuse

 

Shutdown due to high engine

 

• Allow engine to cool, then restart

 

temperature

 

 

 

 

 

• Decrease loads on generator

 

 

 

• Check enclosure openings for blockage

 

 

 

• Check oil cooler for blockage

200-2341

35

Page 35
Image 35