A---19
Powerware 9315 Maintenance Bypass Module 30---160kVA
164201177 Rev. C 041500
Read and understandthe following notes while planning your installation:
1. Refer to national and local electr ic codes for acceptable external wiring practices.
2. Materialand labor for external wiring requirements are to be provided by others.
3. Forexternal wiring requirement, including theminimum AWG size of external wiring,see the appropriate column in TableA ---3.
The power wiring for this equipment is rated at 90 degrees Celsius.
4. The outputof the UPS is not a separately derived source. Output neutral is notbonded to equipment ground through the main
bondingjumper. Refer to NEC and localcodes for proper grounding practices.
5. The maintenance bypass (MBM) source must contain overcurrent protection with the maximum trip setting of 125% of the full
load input current in Table A---3.
6. The Bypassthree-phase feeds should be symmetrical aboutg round.
7. Transferseq uence instructionsfor the MBM are placed on the breaker access panel behind the cabinet doors.
8. Controlwiring must be installed in separate conduitfrom the power wiring.
9. Electronicinterlockis a standard part of the maintenance bypassmodule cabinet. This electronicinterlock can be replacedwith
an optional(extra cost) mechanical interlock if required.
10. Refer toUPS Installation Manual for proper Bypassterminating lugs at UPS cabinet or at inputtransformer cabinet.
11. Refer toTable C---3for control wiring connections.
12. Refer to ParallelRedundant System Manual for details.
LEGEND
MIS: MAINTENANCE ISOLATION BREAKER
MBM: MAIN TENANCE BYPASS BREAKER
BIB: BYPASS INPUT BREAKER
SKRU: SOLENOID KEY RELEASEUNIT
(MECHANICALINTERLOCK)
PTC: PARALLEL TIE CABINET
RT: REVERSE TRANSFER
DESCRIPTION:
DATE:
DRAWINGNO: 1of1
SHEET:
REVISION: A080498
164201177---9ONELINE -- 30-160kVA, PARALLEL, 208:208VAC
110100072