INTEGRATING THE UPS
Table 5. Read Input Registers - Modbus Function Code 04 (Input Registers Start at 30000)
Register | Meter Name | Scale | Unit |
|
|
|
|
|
|
1 | OUTPUT VOLTS AB | /10 | Volts |
|
|
|
|
|
|
2 | OUTPUT VOLTS BC | /10 | Volts |
|
|
|
|
|
|
3 | OUTPUT VOLTS CA | /10 | Volts |
|
|
|
|
|
|
4 | INPUT VOLTS AB | /10 | Volts |
|
|
|
|
|
|
5 | INPUT VOLTS BC | /10 | Volts |
|
|
|
|
|
|
6 | INPUT VOLTS CA | /10 | Volts |
|
|
|
|
|
|
10 | BYPASS VOLTS AB | /10 | Volts |
|
|
|
|
|
|
11 | BYPASS VOLTS BC | /10 | Volts |
|
|
|
|
|
|
12 | BYPASS VOLTS CA | /10 | Volts |
|
|
|
|
|
|
19 | INPUT CURRENT PHASE A | /10 | Amps |
|
|
|
|
|
|
20 | INPUT CURRENT PHASE B | /10 | Amps |
|
|
|
|
|
|
21 | INPUT CURRENT PHASE C | /10 | Amps |
|
|
|
|
|
|
22 | OUTPUT TRUE POWER | /10 | kW |
|
|
|
|
|
|
23 | INPUT TRUE POWER | /10 | kW |
|
|
|
|
|
|
24 | OUTPUT APPARENT POWER | /10 | kVA |
|
|
|
|
|
|
25 | INPUT APPARENT POWER | /10 | kVA |
|
|
|
|
|
|
26 | OUTPUT POWER FACTOR | /100 | — |
|
|
|
|
|
|
27 | INPUT POWER FACTOR | /100 | — |
|
|
|
|
|
|
28 | OUTPUT FREQUENCY | /10 | Hz |
|
|
|
|
|
|
29 | INPUT FREQUENCY | /10 | Hz |
|
|
|
|
|
|
30 | INVERTER FREQUENCY | /10 | Hz |
|
|
|
|
|
|
31 | BYPASS FREQUENCY | /10 | Hz |
|
|
|
|
|
|
33 | BATTERY CURRENT | /10 | Amps |
|
|
|
|
|
|
34 | BATTERY VOLTAGE | /10 | Volts |
|
|
|
|
|
|
35 | % BATTERY LEFT | /10 | % |
|
|
|
|
|
|
36 | BATTERY TIME REMAINING | /10 | Minutes |
|
|
|
|
|
|
60 | INVERTER VOLTS PHASE A | /10 | Volts |
|
|
|
|
|
|
61 | INVERTER VOLTS PHASE B | /10 | Volts |
|
|
|
| ||
| EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.com | 21 |