INTEGRATING THE UPS

Table 5. Read Input Registers - Modbus Function Code 04 (Input Registers Start at 30000)

Register

Meter Name

Scale

Unit

 

 

 

 

 

 

1

OUTPUT VOLTS AB

/10

Volts

 

 

 

 

 

 

2

OUTPUT VOLTS BC

/10

Volts

 

 

 

 

 

 

3

OUTPUT VOLTS CA

/10

Volts

 

 

 

 

 

 

4

INPUT VOLTS AB

/10

Volts

 

 

 

 

 

 

5

INPUT VOLTS BC

/10

Volts

 

 

 

 

 

 

6

INPUT VOLTS CA

/10

Volts

 

 

 

 

 

 

10

BYPASS VOLTS AB

/10

Volts

 

 

 

 

 

 

11

BYPASS VOLTS BC

/10

Volts

 

 

 

 

 

 

12

BYPASS VOLTS CA

/10

Volts

 

 

 

 

 

 

19

INPUT CURRENT PHASE A

/10

Amps

 

 

 

 

 

 

20

INPUT CURRENT PHASE B

/10

Amps

 

 

 

 

 

 

21

INPUT CURRENT PHASE C

/10

Amps

 

 

 

 

 

 

22

OUTPUT TRUE POWER

/10

kW

 

 

 

 

 

 

23

INPUT TRUE POWER

/10

kW

 

 

 

 

 

 

24

OUTPUT APPARENT POWER

/10

kVA

 

 

 

 

 

 

25

INPUT APPARENT POWER

/10

kVA

 

 

 

 

 

 

26

OUTPUT POWER FACTOR

/100

 

 

 

 

 

 

27

INPUT POWER FACTOR

/100

 

 

 

 

 

 

28

OUTPUT FREQUENCY

/10

Hz

 

 

 

 

 

 

29

INPUT FREQUENCY

/10

Hz

 

 

 

 

 

 

30

INVERTER FREQUENCY

/10

Hz

 

 

 

 

 

 

31

BYPASS FREQUENCY

/10

Hz

 

 

 

 

 

 

33

BATTERY CURRENT

/10

Amps

 

 

 

 

 

 

34

BATTERY VOLTAGE

/10

Volts

 

 

 

 

 

 

35

% BATTERY LEFT

/10

%

 

 

 

 

 

 

36

BATTERY TIME REMAINING

/10

Minutes

 

 

 

 

 

 

60

INVERTER VOLTS PHASE A

/10

Volts

 

 

 

 

 

 

61

INVERTER VOLTS PHASE B

/10

Volts

 

 

 

 

 