Chapter 6 Troubleshooting
Problem | Possible Cause | Corrective Action | |
|
|
| |
The Modbus Profiler | The wrong communication port number was | Verify the correct port number on your | |
tool does not | entered in the profiler comX command. | computer that is connected to the Modbus | |
generate the |
| Card. | |
profiler.csv file |
|
| |
The serial cable is not connected. | Verify that the serial cable connections are | ||
| |||
|
| secure. | |
|
|
| |
Communication | Incorrect communication parameters. | Verify that the communication parameters are | |
doesn’t work |
| set to the desired baud rate, No parity, 8 data | |
|
| bits, 1 stop bit, and no hardware handshaking. | |
|
|
| |
| For | ||
|
| master | |
|
| connected to the Modbus Card RxD(+) input | |
|
| signal and the | |
|
| is connected to the Modbus Card | |
|
| signal. | |
|
| For | |
|
| ||
|
| terminal strip or | |
|
| in Table 1 on page 9 or Table 2 on page 10, | |
|
| respectively. | |
|
| See Chapter 3, “Wiring the Modbus Card” on | |
|
| page 7 for more information. | |
|
|
| |
| If the Modbus Card is the last device installed | Verify the termination settings (see | |
| in the network chain or the length of the | “Termination” on page 10 for the correct | |
| network cable is excessive, termination | settings). | |
| needs to be enabled. |
| |
|
|
| |
| J9 and J10 jumpers could be in the incorrect | Verify the jumpers are in the correct position | |
| position for your configuration. | (see Figure 4 on page 5). | |
|
|
| |
| The polling rate in the Building Management | The Modbus Card updates the status of the | |
| Software (BMS) application or Modbus | Eaton equipment every 1000 mS. Configure | |
| software is set below 500 mS. | the BMS/Modbus application polling rate to | |
|
| 500 mS or greater to ensure proper operation. | |
|
|
|
EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.com | 23 |