Powerware FCC 15 manual Press Enter. The Configuration screen appears see Figure

Models: FCC 15

1 32
Download 32 pages 47.58 Kb
Page 18
Image 18

MODBUS CARD CONFIGURATION

2.Press [Enter]. The Configuration screen appears (see Figure 13).

Powerware Modbus Card

Version 1.00 (1-16-02)

Current Configuration:

Baud Rate:

9600

Slave Address:

29

-----------------------------------------------------------------------------

Valid Commands:

 

AD Change Slave Address, usage AD n,

where n is the new slave address for the card (1 - 247 valid). BD Change Modbus Baud Rate, usage BD n,

where n is the new baud rate (1200, 2400, 4800, 9600, 19200). SA Save Configuration

-----------------------------------------------------------------------------

Figure 13. Configuration Screen

If the Configuration screen does not appear, press [Enter] one more time.

If you still do not see the Configuration screen, check the following conditions:

S The communication settings of the terminal should be 9600 baud, No parity, 8 data bits, 1 stop bit, and no hardware handshaking.

S If the serial configuration is correct, check the cabling to be sure all connections are secure.

S Verify that your terminal emulation program is on the correct communication port for serial communication.

S Verify that the UPS has input power and is turned on.

3.To configure the Modbus Card baud rate, type BD followed by a space and the baud rate (1200, 2400, 4800, 9600, or 19200) and press [Enter]. The default is 9600 baud. This setting affects both RS-232 and RS-485 Modbus connections.

14

EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.com

Page 18
Image 18
Powerware FCC 15 manual Press Enter. The Configuration screen appears see Figure