INTEGRATING THE UPS
5.Run profiler from the command prompt or
By default, Modbus Profiler uses the communication port specified in the [Connection] section of the profiler.ini file. If profiler fails to connect using this communication port, you are prompted with a list of alternate communication ports. You may also edit the Port= value in the [Connection] section of the profiler.ini file to change the default value.
6.Modbus Profiler creates an output file named profiler.csv in the directory where the Modbus Profiler tool is located.
Before the program exits, you are prompted to view the data.
The comma delimited file can be easily imported into Microsoft Excel for viewing of the Modbus data. This data is used to create the necessary template files on your Building Management System for polling the desired UPS information.
NOTE Modbus Profiler does not provide Modbus data for the Powerware 9315 Series UPS.
Powerware 9315
Modbus Profiler tool is located (refer to the 950*.pdf files).
Example Modbus Profiler Output Files
The following tables are sample Modbus Profiler output files for a Powerware 9315 Reverse Transfer (RT) Single Module UPS. Refer to the Master Modbus Register Map for a complete list of the Status, Alarm, and Meter data for all Powerware UPS equipment (open the reg_map.pdf file in the directory where the Modbus Profiler tool is located).
Table 4. Read Input Status - Modbus Function Code 02 (Inputs Start at 10000)
Register | Name | Value | Format | Unit | |
|
|
|
|
|
|
1 |
| On Battery | 0 | BOOL | Status |
|
|
|
|
|
|
10 |
| On Bypass | 1 | BOOL | Status |
|
|
|
|
|
|
11 |
| System Normal | 0 | BOOL | Status |
|
|
|
|
|
|
16 |
| UPS Off | 0 | BOOL | Status |
|
|
|
|
|
|
|
| NOTE Registers |
|
|
|
|
|
|
|
|
|
112 |
| Rectifier Status | 1 | BOOL | Status |
|
|
| |||
18 | EATON Powerware® Modbus® Card User’s Guide S 164201376 Rev C www.powerware.com |
|