PVI Industries PV500-12 TURBOPOWER 99 WATER HEATER, 9GAS SUPPLY AND PIPING, Water Heater, Prefix

Models: PV500-12

1 26
Download 26 pages 55.63 Kb
Page 13
Image 13
9GAS SUPPLY AND PIPING

TURBOPOWER 99WATER HEATER

9GAS SUPPLY AND PIPING

Verify that the type of gas specified on rating plate is supplied to the unit. This unit is orificed for operation up to 2000 feet altitude. The appliance Btu/h output, like other similar equipment, derates approximately 4% per 1000 feet above sea level. Consult Factory for installations above 2000 feet elevation.

9.1Inlet Pressure: Measured at the inlet pressure tap located at the main gas cock. The inlet pressure must remain within the minimum flow pressure and maximum static pressure charted below while the unit is at rest and while the unit is operating at maximum firing rate.

Water Heater

Min Inlet Flow Pressure

Prefix

(in. W.C.)

742

5.0" Nat. Gas

1485

5.5" Nat. Gas

2228

6.0" Nat. Gas

2971

11.0" Nat. Gas

Max Static Pressure

(in. W.C.)

14" Nat. Gas

14" Nat. Gas

14" Nat. Gas

14" Nat. Gas

9.2Manifold Pressure: Measure at the pressure tap on the downstream side of the final manual shutoff valve for each stage of operation. The rated manifold pressure appears on the data label. The manifold pressure is preset at the factory and adjustment is not usually required. If adjustment is required, the burner must be firing at the minimum and/or full rate while the manifold pressure is adjusted.

9.3Gas Piping Size: Use the values in “Convert Fittings To Equivalent Straight Pipe” to add the equivalent straight pipe for each elbow or tee to obtain the total distance from the meter. Use this corrected total distance from the meter for determining the suggested pipe size in the “Single Unit Installation Suggested Gas Pipe Size” table.

 

CONVERT FITTINGS TO EQUIVALENT STRAIGHT PIPE

 

 

 

 

Fitting Size (inches)

¾"

 

1"

1¼"

 

1½"

 

2"

 

3"

 

4"

 

5"

 

 

 

Equivalent Length of

2'

 

2'

3'

 

4'

 

5'

 

10'

 

14'

 

20'

 

 

 

Straight Pipe (feet)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SINGLE UNIT INSTALLATION SUGGESTED PIPE SIZE

Equivalent Feet

 

 

Maximum Capacity for Natural Gas*

 

From Meter

MBTU/HR Based on 0.5" W.C. Pressure Drop*

 

 

 

1-1/4"

 

1-1/2"

2"

 

 

2½"

 

 

3"

 

 

4"

25

860

 

1320

 

2475

 

3900

 

7000

 

-

40

660

 

990

 

1900

 

3000

 

5300

 

-

60

-

 

810

 

1520

 

2400

 

4300

 

-

80

-

 

690

 

1300

 

2050

 

3700

 

-

100

-

 

620

 

1150

 

1850

 

3250

 

6700

125

-

 

-

 

 

1020

 

1650

 

2950

 

6000

150

-

 

-

 

 

950

 

1500

 

2650

 

5500

175

-

 

-

 

 

850

 

1370

 

2450

 

5000

200

-

 

-

 

 

800

 

1280

 

2280

 

4600

**Multiplier for alternate pressure drops: 0.3" W.C. 0.77; 1.0" W.C. 1.41; 2.0" W.C. 2.00; and 4.0" W.C. 2.82.

13

PV500-12 08/12

Page 13
Image 13
PVI Industries PV500-12 TURBOPOWER 99 WATER HEATER, 9GAS SUPPLY AND PIPING, Water Heater, Min Inlet Flow Pressure, Prefix