CONFIGURATION SETTINGS TEMPTRAC & XR10CX

CONFIGURATION SETTINGS TEMPTRAC & XR10CX

Dip switches A0 to A7 configure the serial address. The table below lists the settings up to 10. The full 257 address settings can be found in the ProtoCessor Getting Started (T17007) manual at www.protocessor.com

A7

A6

A5

A4

A3

A2

A1

A0

Address

Off

Off

Off

Off

Off

Off

Off

Off

0

Off

Off

Off

Off

Off

Off

Off

On

1

Off

Off

Off

Off

Off

Off

On

Off

2

Off

Off

Off

Off

Off

Off

On

On

3

Off

Off

Off

Off

Off

On

Off

Off

4

Off

Off

Off

Off

Off

On

Off

On

5

Off

Off

Off

Off

Off

On

On

Off

6

Off

Off

Off

Off

Off

On

On

On

7

Off

Off

Off

Off

On

Off

Off

Off

8

Off

Off

Off

Off

On

Off

Off

On

9

Off

Off

Off

Off

On

Off

On

Off

10

Dip switches B0 to B3 configure baud rate.

The table below lists the settings.

Baud

B3

B2

B1

B0

Auto3

Off

Off

Off

Off

110

Off

Off

Off

On

300

Off

Off

On

Off

600

Off

Off

On

On

1200

Off

On

Off

Off

2400

Off

On

Off

On

4800

Off

On

On

Off

9600

Off

On

On

On

19200

On

Off

Off

Off

20833

On

Off

Off

On

28800

On

Off

On

Off

38400

On

Off

On

On

57600

On

On

Off

Off

76800

On

On

Off

On

115200

On

On

On

Off

Off‐‐‐On

Dip switches S0 to S3 select the register profile to be used. When switch S0 is On the register profile will only monitor one control with an node address of 1. All registers are analog/16bit.

When switch S0 is Off and S1 is On the register profile will monitor up to 8 controls. The register addresses are detailed below. The respective node addresses are 1 to 8.

Control

Discription

Modbus

BACnet

 

 

Address

Address

Temptrac

Set Point Read/Write

40769

1

Temptrac

Temp. Probe 1 Read Only

40257

90

Temptrac

Temp. Probe 2 Read Only

40259

91

Temptrac

Temp. Probe 3 Read Only

40261

92

Temptrac

On/Off Enable Read/Write

401281

95

XR10CX

Temp. Probe 1 Read Only

40257

90

XR10CX

Set Point Read/Write

40854

101

PVI Industries, LLC P.O. Box 7124 Ft. Worth, TX 76111 1‐800‐433‐5654