![CONFIGURATION SETTINGS TEMPTRAC & XR10CX](/images/new-backgrounds/53551/535515x1.webp)
CONFIGURATION SETTINGS TEMPTRAC & XR10CX
Dip switches A0 to A7 configure the serial address. The table below lists the settings up to 10. The full 257 address settings can be found in the ProtoCessor Getting Started (T17007) manual at www.protocessor.com
A7 | A6 | A5 | A4 | A3 | A2 | A1 | A0 | Address |
Off | Off | Off | Off | Off | Off | Off | Off | 0 |
Off | Off | Off | Off | Off | Off | Off | On | 1 |
Off | Off | Off | Off | Off | Off | On | Off | 2 |
Off | Off | Off | Off | Off | Off | On | On | 3 |
Off | Off | Off | Off | Off | On | Off | Off | 4 |
Off | Off | Off | Off | Off | On | Off | On | 5 |
Off | Off | Off | Off | Off | On | On | Off | 6 |
Off | Off | Off | Off | Off | On | On | On | 7 |
Off | Off | Off | Off | On | Off | Off | Off | 8 |
Off | Off | Off | Off | On | Off | Off | On | 9 |
Off | Off | Off | Off | On | Off | On | Off | 10 |
Dip switches B0 to B3 configure baud rate.
The table below lists the settings.
Baud | B3 | B2 | B1 | B0 |
Auto3 | Off | Off | Off | Off |
110 | Off | Off | Off | On |
300 | Off | Off | On | Off |
600 | Off | Off | On | On |
1200 | Off | On | Off | Off |
2400 | Off | On | Off | On |
4800 | Off | On | On | Off |
9600 | Off | On | On | On |
19200 | On | Off | Off | Off |
20833 | On | Off | Off | On |
28800 | On | Off | On | Off |
38400 | On | Off | On | On |
57600 | On | On | Off | Off |
76800 | On | On | Off | On |
115200 | On | On | On | Off |
Off‐‐‐On
Dip switches S0 to S3 select the register profile to be used. When switch S0 is On the register profile will only monitor one control with an node address of 1. All registers are analog/16bit.
When switch S0 is Off and S1 is On the register profile will monitor up to 8 controls. The register addresses are detailed below. The respective node addresses are 1 to 8.
Control | Discription | Modbus | BACnet |
|
| Address | Address |
Temptrac | Set Point Read/Write | 40769 | 1 |
Temptrac | Temp. Probe 1 Read Only | 40257 | 90 |
Temptrac | Temp. Probe 2 Read Only | 40259 | 91 |
Temptrac | Temp. Probe 3 Read Only | 40261 | 92 |
Temptrac | On/Off Enable Read/Write | 401281 | 95 |
XR10CX | Temp. Probe 1 Read Only | 40257 | 90 |
XR10CX | Set Point Read/Write | 40854 | 101 |
PVI Industries, LLC P.O. Box 7124 Ft. Worth, TX 76111 1‐800‐433‐5654 | ||
Page 3 | 7/10 |