POWERING UP THE PROTOCESSOR/PROTONODE

POWERING UP THE PROTOCESSOR/PROTONODE

Power LED comes on and remains solid

LA starts flashing about once per second. This tells us that PIC (Peripheral Interface Controller) number 1 in the ProtoCessor has powered up successfully.

LB starts flashing about once per second. This tells us that PIC number 2 in the ProtoCessor has powered up successfully.

GP105 will go on solid within 45 – 60 seconds after power up, signifying normal operation. ProtoCessor will be able to come up in RUINET shortly after this LED comes on. During the first 45‐60 seconds the LED should be dark.

Upon successful operation of GP105 the ProtoCessor will go through diagnostics of the field port communications.

The FFP‐ETH module is operational after this point.

RX Field Port LED: On normal operation, the RX LED will flash when a message is received on the field port of the ProtoCessor.

TX Field Port LED: On normal operation, the TX LED will flash when a message is sent on the field port of the ProtoCessor.

RX

TX

PWR

GP105

LA

LB

PVI Industries, LLC P.O. Box 7124 Ft. Worth, TX 76111 1‐800‐433‐5654