Quadra-Fire QVI-30FB-S Termination Locations, A. Vent Termination Minimum Clearances, Roof Pitch

Models: QVI-30FB-S

1 41
Download 41 pages 51.75 Kb
Page 9
Image 9
4 Termination Locations

4 Termination Locations

A. Vent Termination Minimum Clearances

Figure 4.1 specifies minimum vent heights for various pitched roofs.

HORIZONTAL

OVERHANG

A. Vent Termination Minimum Clearances WARNING

Fire Risk.

Asphyxiation Risk.

Terminations MUST meet minimum clearances.

Exhaust gases are hot.

Nearby vents may draw fumes into house.

2FT.

MIN.

GAS DIRECT VENT

TERMINATION CAP

20 INCHES MIN.

VERTICAL

LOWEST

WALL

 

DISCHARGE

 

OPENING

 

X

12

Fire Risk. ROOF PITCH

IS X/ 12

H (MIN.) - MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING

Roof Pitch

H (Min.) Ft.

Flat to 6/12

1.0*

Over 6/12 to 7/12

1.25*

Over 7/12 to 8/12

1.5*

Over 8/12 to 9/12

2.0*

Over 9/12 to 10/12

2.5*

Over 10/12 to 11/12

3.25

Over 11/12 to 12/12

4.0

Over 12/12 to 14/12

5.0

Over 14/12 to 16/12

6.0

Over 16/12 to 18/12

7.0

Over 18/12 to 20/12

7.5

Over 20/12 to 21/12

8.0

* 3 foot minimum in snow regions

Figure 4.1 Minimum height from roof to lowest discharge opening

Quadra-FireQVI-30FB-S2020-910 Rev. H • 6/09

9

Page 9
Image 9
Quadra-Fire QVI-30FB-S Termination Locations, A. Vent Termination Minimum Clearances, Fire Risk Asphyxiation Risk, 1.25