TECHNICAL DATA

MOD.

 

120

130

140

160

190

210

240

260

Refrigerant

 

R407C

R407C

R407C

R407C

R407C

R407C

 

 

 

 

 

 

 

 

 

 

 

 

Cooling capacity

kW

115,5

128

142

156

181

206,1

###

###

Compressor input power

kW

38

42,1

47,3

51,7

59,7

67,8

 

 

Water flow rate

l/h

20640

22190

24600

27180

31990

36290

 

 

 

 

 

 

 

 

 

 

 

 

Water pressure drop

kPa

29,4

30,0

30,8

36,0

39,6

42,7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating capacity

kW

120

132

150

165

189

217

 

 

Compressor input power

kW

38,5

42,9

48,1

52,8

60,6

68,4

 

 

 

 

 

 

 

 

 

 

 

 

Water flow rate

l/h

20640

22700

25800

28380

32510

37320

 

 

Water pressure drop

kPa

29,4

31,3

33,8

39,2

40,9

45,1

 

 

 

 

 

 

 

 

 

 

 

 

Total input current (K version)

A

76,4

85,5

96,3

104,7

126,6

144

 

 

Total peak current

A

322,1

333,1

290

304

351

369

 

 

Maximum input current

A

102,1

113,1

119,9

138,3

167,6

185,6

 

 

Power supply

V/Ph/Hz

 

 

 

400/3/50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

m°/h

33000

33000

33000

33000

64000

62000

 

 

Fans

n° x kW

3 x 1.23

3 x 1.23

3 x 1.23

3 x 1.23

4 x 1,25

4 x 1,25

 

 

 

 

 

 

 

 

 

 

 

Compressors

type

 

 

 

Scroll

 

 

 

2

2

4

4

4

4

 

 

 

 

 

Refrigerant circuits

1

1

2

2

2

2

 

 

 

 

 

 

 

 

 

 

 

 

Control steps

2

2

4

4

4

4

 

 

 

 

 

 

 

 

 

 

 

 

Sound power level (1)

dB(A)

80,1

80,5

81

81,3

84

84

 

 

Sound pressure level (2)

dB(A)

52,1

52,5

53

53,3

58

58

 

 

 

 

 

 

 

 

 

 

 

 

Water pump (option)

kW

2,2

2,2

2,2

3,0

3,0

3,0

 

 

Pump available pressure (option)

kPa

120

130

105

180

140

110

 

 

 

 

 

 

 

 

 

 

 

 

Water tank capacity (option)

l

530

530

530

670

670

670

 

 

 

 

 

 

 

 

 

 

 

 

Expansion vessel (option)

l

18

18

18

18

18

18

 

 

 

 

 

 

 

 

 

 

 

 

Length

mm

3608

3608

4108

4108

4708

4708

 

 

Width

mm

1105

1105

1105

1105

1105

1105

 

 

Height

mm

1842

1842

2262

2262

2262

2262

 

 

Weight (Standard configuration)

kg

1200

1230

1650

1700

1960

2050

 

 

Weight (with hydraulic kit)

kg

1410

1440

1860

2000

2260

2350

 

 

 

 

 

 

 

 

 

 

 

 

## # XL Models in these sizes are available as a special unit. Contact QUARTZ technical department for details. Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Heating: ambient air temperature 8.3 °C db, 6.1 °C wb ; condenser water temperature in/out 40°C / 45 °C.

(1): Sound power level according to ISO 3746.