Refrigerant charge checking

A few minutes after start up, working on cooling operating mode, check that condensing temperature, is approximately 15 °C higher than condenser inlet air temperature. Also check that the evaporation temperature is about 5 °C lower than the evaporator outlet temperature.

When the unit has stabilised, check that the sight glass core shows green: if the core is yellow, moisture is present in the circuit. In this case it is necessary to dehydrate the circuit (qualified personnel only). Check at the sight glass that there are no continuous vapour bubbles present. If so, additional refrigerant charge may be required. (A few vapour bubbles are acceptable).

Check that refrigerant superheat on the evaporator is about 5-7 °C

Check if refrigerant sub-cooling on the condenser is about 5-7 °C.

Unit switch OFF

Please refer to the microprocessor manual enclosed with the unit.

Caution: For temporary stops (night time, weekend etc.) never switch off the unit by opening the mains

switch: this should only be used to disconnect the unit from the power supply when current is not passing through it, i.e. when the unit is in ‘OFF’ mode. Additionally, with no supply to the crankcase heater, the compressor could be seriously damaged at unit start up.

CONTROL AND SAFETY DEVICE SETTINGS

Control devices - factory settings

CAPACITY STEPS

 

 

 

 

 

 

2

 

 

 

 

4

 

CONTROL DEVICE

 

 

 

 

 

 

Set-point

 

Differential

Set point

 

 

Differential

Control thermostat (cooling)

 

 

°C

 

 

10

 

 

2

 

9

 

 

3

Control thermostat (heating)

 

 

°C

 

 

42

 

 

2

 

43

 

3

Safety devices - factory settings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL DEVICE

 

 

 

 

SET POINT

 

 

DIFFERENTIAL

 

RESET TYPE

Anti-freeze thermostat

°C

 

 

 

4

 

 

6

 

 

 

Manual

Electric heater thermostat

°C

 

 

 

4

 

 

6

 

 

 

Manual

High pressure switch

bar

 

 

 

28

 

 

7

 

 

 

Manual

Low pressure switch

bar

 

 

 

0,7

 

 

1

 

 

 

Manual

End defrosting pressure

bar

 

 

 

18

 

 

--

 

 

Automatic

Defrosting set-point

bar

 

 

 

16

 

 

2

 

 

Automatic

Water safety valve (Optional)

bar

 

 

 

6

 

 

--

 

 

 

--

29