(QLAC / FC FREE COOLING VERSION)
FREE COOLING SYSTEMS MUST ALWAYS BE FILLED WITH GLYCOL SOLUTION
The free cooling versions can operate in 3 different operating modes. The
Cooling mode (Summer operation) Ambient temperature is higher than the return water temperature. In this case, the ambient conditions are not suitable to allow Free Cooling operation; the 3 way valve is closed and the water flows to the evaporator, where it is cooled. The compressors, fans, and the water pump are activated; the unit operates like a normal liquid cooler.
Free cooling mode (Winter operation) Ambient temperature is much lower than the return water temperature. In this case, the ambient conditions are suitable to allow Free Cooling operation; the 3 way valve opens and the water flows into the free cooling coil, where the ambient conditions are sufficient to give the total required load. In this case the pump and the fans are in operation, while the compressors are stopped. In this case, the free cooling system works in substitution of the water chiller.
Cooling mode + Free cooling
CONDENSING PRESSURE CONTROL (optional)
If unit operation below 20°C is expected, a condensing pressure control must be fitted in the unit. This device will allow unit operation under low ambient temperature, by reducing condenser air flow and obtaining acceptable operating parameters. This device modulates the fan speed in proportion to the condensing pressure measured by the pressure transducer.
This device is factory
OPERATIONAL LIMITS
Evaporator water flow rate
The nominal water flow rates are based on a delta T (Win - Wout) of 5 °C. The maximum flow rate allowed is that achieved with a delta T of 3 °C: higher values may cause too high pressure drop. The minimum water flow rate allowed is that achieved with a delta T of 8 °C. Insufficient values cause too low evaporating temperatures, tripping safety devices which stop the unit.
Chilled water temperature (summer operation)
The minimum temperature allowed at the evaporator outlet is 5 °C. To work below this limit, the unit requires modification - please contact TEV Ltd. The maximum temperature allowed at the evaporator inlet is 20 °C.
Hot water temperature (winter operation)
Once the system is at temperature, the water temperature at the condenser inlet should not be less than 23 °C: lower values could cause incorrect working operation of the compressor and compressor failure may occur. The maximum water temperature at the condenser outlet should not exceed 48 °C: higher values will cause safety devices to trip and stop operation.
Ambient air temperature
The units are designed and manufactured to operate, in cooling, with ambient air temperature between 20°C to 42 °C If a fan speed control is installed then the minimum ambient air temperature is