Quartz TECHNICAL MANUAL AIR COOLED WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS, 06617645-02

Models: TECHNICAL MANUAL AIR COOLED WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS 06617645-02

1 42
Download 42 pages 62.46 Kb
Page 9
Image 9

WATER CHILLERS AND HEAT PUMPS

QLAC / LS (Low noise version)

TECHNICAL DATA

MOD.

 

300

320

 

380

430

500

Refrigerant

 

R407C

R407C

R407C

R407C

R407C

 

 

 

 

 

 

 

 

Cooling capacity

kW

290

321

 

383

432

481

Compressor input power

kW

92,4

100,6

 

126,4

138,7

150,9

Water flow rate

l/h

49880

55200

 

65800

74300

82700

 

 

 

 

 

 

 

 

Water pressure drop

kPa

34

39

 

32

38

44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Free cooling capacity

kW

185

185

 

235

245

240

input power

kW

12

12

 

16

16

16

 

 

 

 

 

 

 

 

Water flow rate

l/h

49880

55200

 

65800

74300

82700

Water pressure drop

kPa

107

121

 

113

121

141

 

 

 

 

 

 

 

 

Total input current (K version)

A

201,4

220

 

279,2

301,7

324,2

Total peak current

A

510

534

 

582

641

672,5

Maximum input current

A

262,6

287,2

 

362

393,5

425

Power supply

V/Ph/Hz

 

 

400/3/50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow

m°/h

89000

88500

 

119000

118000

118000

Fans

n° x kW

6x2

6x2

 

8x2

8x2

8x2

 

 

 

 

 

 

 

 

Compressors

type

 

 

 

Scroll

 

 

4

4

 

6

6

6

 

 

Refrigerant circuits

2

2

 

2

2

2

 

 

 

 

 

 

 

 

Control steps

4

4

 

6

6

6

 

 

 

 

 

 

 

Sound power level (1)

dB(A)

90

90

 

91

91

91

Sound pressure level (2)

dB(A)

62

62

 

63

63

63

 

 

 

 

 

 

 

Water pump (option)

kW

4

5,5

 

7,5

7,5

7,5

Pump available pressure (option)

kPa

160

172

 

210

190

160

 

 

 

 

 

 

 

 

Water tank capacity (option)

l

670

670

 

670

670

670

 

 

 

 

 

 

 

 

Expansion vessel (option)

l

25

25

 

50

50

50

 

 

 

 

 

 

 

Length

mm

4108

4108

 

4708

4708

4708

Width

mm

2201

2201

 

2201

2201

2201

Height

mm

2262

2262

 

2262

2262

2262

Weight (Standard configuration)

kg

2750

2800

 

3100

3150

3210

Weight (with hydraulic kit)

kg

3150

3220

 

3550

3610

3690

 

 

 

 

 

 

 

 

Performances are rated at:

Cooling: ambient air temperature 35 °C; evaporator water temperature in/out 12°C / 7 °C.

Free cooling: ambient air temperature 2 °C; water inlet temperature 15°C, glycol 20%, nominal waterflow, compressors switched off

(1): Sound power level according to ISO 3746.

(2): Sound pressure level measured at 10m from the unit in free field conditions: direction factor Q=2 (according to ISO 3746).

9

06617645-02

Page 9
Image 9
Quartz TECHNICAL MANUAL AIR COOLED WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS, 06617645-02 300 320 380 430 500