Rackmount Solutions VA 20000 manual UPS Model Active, Mechanical Data, Battery extension, Signals

Models: VA 2000 VA 10000 VA 700 VA 3000 VA 20000 VA 6000 VA 1000

1 58
Download 58 pages 34.11 Kb
Page 27
Image 27

Table 5. Chloride Active UPS North America

UPS Model

Active 700

 

Active 1000

Active 2000

 

Active 3000

 

 

 

 

 

 

 

 

 

 

 

 

Efficiency

 

> 83%

 

 

 

 

 

 

 

Protection class

 

 

IP 20

 

 

 

 

 

 

Cooling

 

 

Fan

 

 

 

 

 

 

 

 

Noise level mains operation

< 41 dBa

 

< 41 dBa

< 50 dBa

 

< 50 dBa

 

 

 

 

 

 

 

Noise level battery operation

< 45 dBa

 

<45 dBa

< 50 dBa

 

<50 dBa

 

 

 

 

 

 

Operating temperature (ambient)

 

+ 50°F to +105°F (10°C to + 40°C)

recommended +59°F to +89°F (+15°C to + 32°C)

 

 

 

 

 

Storage temperature

 

+5°F to +104°F (-15°C to +40°C)

 

 

 

 

 

 

Relative humidity

 

 

20% to 90%,non-condensation

 

 

 

 

 

 

 

 

 

max. 10,000 ft. (3000m),

 

Altitude

above 5,000 ft. (1500m) max ambient temperature = 95°F

 

 

 

(35 °C)

 

 

 

 

 

 

 

 

Mechanical Data

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight - lbs. (kg)

28.6 (13)

 

35.3 (16)

75 (34)

 

75 (34)

 

 

 

 

 

Dimensions - HxWxD in. (mm)

8.9 x 5.7 x 16 (225 x 145 x

13.8 x 7.9 x 18.5 (350 x 200

405)

x 470)

 

 

 

 

 

 

 

 

Battery extension

 

 

 

 

 

 

 

 

 

 

 

 

 

Type

None

 

BPActive

BPActive

 

BPActive

 

1000

3000

 

3000

 

 

 

 

 

 

 

 

 

 

 

Weight lbs (kg)

None

 

42 (19)

106 (48)

 

106 (48)

 

 

 

 

 

 

 

 

 

 

8.9 x 5.7 x

 

 

 

Dimensions - HxWxD in. (mm)

None

 

16

13.8 x 7.9 x 18.5

 

(225x145x4

(350 x 200 x 470)

 

 

 

 

 

 

05)

 

 

 

 

 

 

 

 

 

 

Signals

 

 

 

 

 

 

 

 

 

 

 

 

 

Visual

 

 

LED-indication at the front side

 

 

 

 

 

 

Audible

 

 

Acoustical alarm

 

 

 

 

 

 

 

 

 

RS232 interface

 

Communications

 

 

Alarm contacts +5V...+12 V

 

 

 

Signal input +5V...+12 V

 

 

 

 

 

 

 

 

Ethernet (optional)

 

 

 

 

 

 

 

 

Chloride Active and E-Series UPS User Manual

23

Page 27
Image 27
Rackmount Solutions VA 20000, VA 3000, VA 700, VA 10000 manual UPS Model Active, Mechanical Data, Battery extension, Signals