| FRONT VIEW | |
|
|
|
|
TOP VIEW
Fig. 7: Minimum Clearances from Combustible
When installed according to the listed minimum clear- ances from combustible construction, these heaters can still be serviced without removing permanent structural construction around the heater. However, for ease of servicing, we recommend a clearance of at least 24 in. in front, and at least 36 in. on the water connection side. This will allow the heater to be serv- iced in its installed location without movement or removal of the heater.
Service clearances less than the minimums may require removal of the heater to service either the heat exchanger or the burner tray. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure
around the | heater. | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Outdoor Installations
These heaters are
| Heater | Min. Clearance | Recommended |
|
| ||||||
| from Combustible |
| Service |
|
| ||||||
| Side |
|
|
| |||||||
| Surfaces |
| Clearance |
|
| ||||||
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| Front | Open |
|
|
| 24” |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Rear | 12” |
|
|
| 24” |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Water Side | 36” |
|
|
| 36” |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Other Side | 36” |
|
|
| 36” |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Top | Unobstructed |
|
|
| 36” |
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
| Vent | N/A |
|
|
| N/A |
|
| |||
|
|
|
| ||||||||
|
|
| |||||||||
| Table E: | Clearances – Outdoor Installations |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 8: Minimum Clearances from Combustible
10