Venting Installation Tips

Venting Installation Tips

Support piping:

·horizontal runs- at least every five (5) feet.

·vertical runs - use braces:

·under or near elbows

Follow items listed below to avoid personal injury or property damage.

·Cut nonmetallic intake pipe with fine-toothed hack- saw.

·Do not use nonmetallic intake pipe or fittings that are cracked or damaged.

·Do not use nonmetallic intake fittings if they are cut or altered.

·Do not drill holes, or use screws or rivets, in non- metallic intake pipe or fittings.

To make metallic vent joints:

·Do not install seams of vent pipe on bottom of runs.

·100% Seal all joints and seams with high temper- ature silicone sealant.

WARNING: Examine the venting system at least once a year. Check all joints and vent pipe connections for tightness, corrosion or deterioration.

NOTE: The words "Flue Exhaust", "Flue" and "Exhaust Vent" are used interchangeably.

on, Venting of Equipment, of the latest edition of NFGC, or in Canada, B149 Installation Code for Gas Burning Appliances and Equipment, or applicable pro- visions of local building codes.

10 FEET 

OR LESS

VENT CAP

2' MIN.

2' MIN.

VENT PIPE

COMBUSTION AIR

FILTER

BOILER 

UNIT

Venting Configurations

 

 

 

For heaters connected to gas vents or chimneys, vent

 

 

installations shall be in accordance with the section

Fig. 18: Natural Draft Vertical Venting (Category I)

 

 

 

 

 

Certified

Minimum

Min./Max. Venting

Model

Appliance

Length without

Venting

Recommended

No.

Category

Barometric

Material

Vent Size (inches)

 

 

Damper (feet)**

 

 

 

 

122

 

 

4

 

162

 

Type B or

 

 

202

I

5

5/25

Equivalent

242

 

 

 

 

 

 

 

322

 

 

6

 

**Vent lengths are based on a lateral length of 2 feet. Refer to the latest edition of the NFGC for fur- ther details. (ANSI Z223.1)

Table J: Natural Draft Vertical Venting

25

Page 25
Image 25