Raypak 122-322 manual Controls, High Limit Manual Reset, Ignition Control Module

Models: 122-322

1 44
Download 44 pages 22.92 Kb
Page 33
Image 33
CONTROLS

CONTROLS

WARNING: Installation, adjustment and service of heater controls including timing of various operating functions must be performed by a qualified installer, service agency or the gas supplier. Failure to do so may result in control damage, heater malfunction, property damage, personal injury, or death.

WARNING: Turn off the power to the heater before installation, adjustment or service of the heater controls. Failure to do so may result in heater malfunction, property damage, personal injury, or death.

CAUTION: This appliance has provisions to be connected to more than one (1) supply source. To reduce the risk of electric shock, disconnect all such connections before servicing.

CAUTION: Risk of electric shock. More than one

(1)disconnect switch may be required to de- energize the equipment before servicing.

Fig. 22: Ignition Module

High Limit (Manual Reset)

The heater is equipped with a manual reset high limit temperature device. Push the reset button and adjust the setting to 30° F or 40° F above desired operating temperature.

Ignition Control Module

The interrupted proved ignition device conserves ener- gy. When additional heat is needed, the combustion air blower starts to purge all air from the combustion chamber for about 15 seconds. On proof of air flow, the air proving switch closes and the igniter is ener- gized, eliminating the fuel costs of maintaining a constant pilot.

Fig. 23: Manual Reset High Limit

To ensure safe operation, the gas valve cannot open until the pilot igniter is verified. The 100% igniter safe- ty is an electronic device which closes the main gas valve within 8/10 of a second whenever the flame is interrupted. Main burner is automatically lit when the device is powered and pre-purged. Unit performs its own safety check and opens the main valve only after the igniter is proven to be capable of ignition.

33

Page 33
Image 33
Raypak 122-322 manual Controls, High Limit Manual Reset, Ignition Control Module