Piping—Heating Boilers

Piping—Heating Boilers

All high points should be vented. Purge valves and a bypass valve should be installed. A boiler installed above radiation level must be provided with a low water cut-off device. The boiler, when used in connec- tion with a refrigeration system, must be installed so the chilled medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler.

The boiler piping system of a hot water heating boiler connected to heating coils located in air handling units where they may be exposed to circulating refrigerated air, must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. It is highly recom- mended that the piping be insulated.

Air-Separation/Expansion Tank

All boilers should be equipped with a properly sized expansion tank and air separator fitting as shown in the diagrams.

Three-Way Valves

Valves designed to blend water temperatures or reduce water circulation through the boiler should not be used. Raypak boilers are high recovery low mass boilers not subject to thermal shock. Raypak offers a full line of electric sequencers that produce direct reset of boiler water temperature. Refer to the Controls Section in our Complete Catalog.

Domestic Hot Water Piping

When designing the water piping system for domestic water applications, water hardness should be consid- ered. Table G indicates the suggested flow rates for soft, medium and hard water. Hardness is specified as grains per gallon.

Model

Soft (0–4 grains per gallon)

Medium (5–15 grains per gallon)

Hard* (16–25** grains per gallon)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ΔT

gpm

ΔP

MTS

SHL

ΔT

gpm

ΔP

MTS

SHL

ΔT

gpm

ΔP

MTS

SHL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

122

10

20

2.5

1-1/4

4.9

8

26

4.0

1-1/4

7.8

7

30

5.3

1-1/4

10.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

162

14

20

2.5

1-1/4

4.9

11

26

4.1

1-1/4

7.9

9

30

5.4

1-1/4

10.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

202

17

20

2.6

1-1/4

5.0

13

26

4.2

1-1/4

8.0

11

30

5.5

1-1/4

10.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

242

21

20

2.6

1-1/2

3.5

16

26

4.3

1-1/2

5.9

9

44

11.8

1-1/2

16.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

322

27

20

2.7

1-1/2

3.6

20

27

4.8

1-1/2

6.6

12

44

12.2

1-1/2

16.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ΔT = Temperature rise, °F.

ΔP = Pressure drop through heat exchanger, ft.

SHL = System head loss, ft. (System head loss is based on the heater and tank placed no more than 5 feet apart and 25 feet equivalent length of pipe and fittings.)

gpm = Gallons per minute, flow rate.) MTS = Minimum tubing size.

*Must utilize optional cupro-nickel tubes.

**With Hard Water (16-25 grains per gallon), the operating control must be set no higher than 130F for scale free operation. For operating temper- atures above 130F, a water softener must be utilized.

Table G: Domestic Water Heater Flow Rate Requirements

15

Page 15
Image 15
Raypak 122-322 manual Domestic Hot Water Piping, Piping-HeatingBoilers, Air-Separation/ExpansionTank, Three-WayValves