Raypak 260-401 manual 3Pilot Outage

Models: 260-401

1 36
Download 36 pages 35.99 Kb
Page 27
Image 27

3)Pilot Outage.

1) Too low or too high gas

1)

Adjust inlet gas pressure as

 

(Standing pilot models)

 

pressures.

 

shown on rating plate.

 

 

2)

Restricted pilot.

2)

Clean pilot orifice.

 

 

3)

Weak thermocouple.

3)

Replace thermocouple.

 

 

 

 

 

4)Yellow lazy flame.

1) Too low gas pressure.

1) Adjust manifold pressure as

 

 

2)

Restricted burner intake ports.

 

shown on rating plate.

 

 

2) Clean burners free of debris or

 

 

3)

Restricted gas line.

 

insects.

 

 

3) Clean gas line or increase gas line

 

 

 

 

 

piping.

 

 

 

 

 

 

5)Sooting

1) Insufficient combustion air.

1)

Refer to installation instructions

 

 

 

 

 

regarding combustion air

 

 

 

 

 

requirements.

 

 

2)

Improper venting.

2)

Refer to installations instructions.

 

 

3) Severe yellow burner flames.

3)

See yellow flame section above.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

27

Page 27
Image 27
Raypak 260-401 manual 3Pilot Outage