Raypak 399B-2339B operating instructions Gas Supply Connection

Models: 399B-2339B

1 52
Download 52 pages 62.66 Kb
Page 19
Image 19
Gas Supply Connection

regulator must be installed to reduce the gas supply pressure to a maximum of 10.5 in. WC for natural gas and 13.0 in. WC for propane gas. The regulator should be placed a minimum distance of 10 times the pipe diameter up-stream of the heater gas controls. Refer to Table I for maximum pipe lengths.

Gas Supply Connection

CAUTION: The heater must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 psi (3.45 kPa).

The heater must be isolated from the gas supply pip- ing system by closing the manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa). Relieve test pressure in the gas supply line prior to reconnecting the heater and its manual shut-off valve to the gas supply line. FAILURE TO FOLLOW

THIS PROCEDURE MAY DAMAGE THE GAS VALVES. Over pressurized gas valves are not cov- ered by warranty. The heater and its gas connections shall be leak-tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use an open flame.

Fig. 14: Gas Supply Connection

CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural and propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.

Model

 

3/4”

 

1”

1-1/4”

1-1/2”

 

2”

2-1/2”

 

3”

 

4”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

N

 

P

N

 

P

N

P

N

P

N

 

P

N

P

N

 

P

N

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

399B

 

 

15

25

 

60

100

260

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

499B

 

 

 

 

 

 

65

150

130

360

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

649B

 

 

 

 

 

 

45

100

95

250

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

749B

 

 

 

 

 

 

35

80

75

180

260

 

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

899B

 

 

 

 

 

 

20

45

45

110

150

 

360

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

989B

 

 

 

 

 

 

 

 

 

 

120

 

300

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1259B

 

 

 

 

 

 

 

 

 

 

75

 

180

170

325

560

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1529B

 

 

 

 

 

 

 

 

 

 

50

 

120

125

250

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1799B

 

 

 

 

 

 

 

 

 

 

40

 

100

100

225

340

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1999B

 

 

 

 

 

 

 

 

 

 

30

 

80

75

175

260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2069B

 

 

 

 

 

 

 

 

 

 

30

 

80

75

175

260

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2339B

 

 

 

 

 

 

 

 

 

 

20

 

55

55

135

160

 

400

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural gas – 1,000 BTU per ft3, .60 specific gravity at 0.5 in. WC pressure drop

Propane gas – 2,500 BTU per ft3, 1.53 specific gravity at 0.6 in. WC pressure drop

Table I: Maximum Equivalent Pipe Length

19

Page 19
Image 19