Raypak 399B-2339B operating instructions Certified

Models: 399B-2339B

1 52
Download 52 pages 62.66 Kb
Page 31
Image 31
Manual background

 

Certified

 

Maximum

Combustion

 

Air Inlet Max. Length*

 

Model

Vent

Air

 

 

Venting

Equivalent

 

 

 

 

 

 

No.

Size

Intake Pipe

 

 

 

 

 

 

Material

Vent Length*

6”

 

8”

10”

 

12”

 

 

Material

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

399B

 

 

 

 

100’

 

 

 

 

 

 

 

6”

 

 

 

 

 

 

 

 

499B

 

 

 

75’

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

649B

 

 

 

 

 

 

100’

 

 

 

 

 

 

 

 

40’

 

 

 

 

 

749B

 

8”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

899B

 

 

 

 

30’

 

80’

 

 

 

 

 

 

70’Room Air

Galvanized

 

 

 

 

 

 

989B

 

10”

 

 

 

 

 

 

Category III

 

Steel,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1259B

 

 

40’ Ducted

PVC, ABS,

 

 

 

75’

 

100’

 

 

Combustion Air

CPVC

 

 

 

 

 

 

12”

 

 

 

 

 

 

1529B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1799B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1999B

 

14”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40’

 

75’

2069B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2339B

 

16”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Subtract 10 ft per elbow. Max. 3 elbows.

Maximum combustion air duct length terminated at 100 equivalent ft.

Table M: Category III Horizontal and Direct Venting

The vent must be installed to prevent flue gas leakage. Care must be taken during assembly to ensure that all joints are sealed properly and are airtight. The vent must be installed to prevent the potential accumulation of condensate in the vent pipes. It is required that:

1.The vent must be installed with a slight downward slope of not more than 1/4 inch per foot of hori- zontal run to the vent terminal.

2.The vent must be insulated through the length of the horizontal run.

For installations in extremely cold climate, it is re- quired that:

1.The vent must be installed with a slight upward slope of not more than 1/4 inch per foot of hori- zontal run to the vent terminal. In this case, an approved condensate trap must be installed per applicable codes.

2.The vent must be insulated through the length of the horizontal run.

Termination

The flue direct vent cap MUST be mounted on the ex- terior of the building. The direct vent cap cannot be installed in a well or below grade. The direct vent cap must be installed at least 1 ft above ground level and above normal snow levels. The Raypak-approved stainless steel flue direct vent cap must be used (sales order option D-15).

WARNING: No substitutions of flue pipe or vent cap material are allowed. Such substitutions would jeopardize the safety and health of inhabitants.

Use only the special gas vent pipes listed for use with Category III gas burning heaters, such as the AL29-4C stainless steel vents offered by Heat Fab Inc. (800- 772-0739), Protech System, Inc. (800-766-3473), Z-Flex (800-654-5600) or American Metal Products (800-423-4270). Pipe joints must be positively sealed. Follow the vent manufacturer’s installation instructions carefully.

31

Page 31
Image 31
Raypak 399B-2339B operating instructions Certified