MODELS 181-401 and 182-400

VENT TERMINAL/INDOOR STACK

INSTALLATION

1.Remove the louvered jacket top by removing four (4) #10 flathead screws.

2.If originally installed, remove "Pagoda" top from the louvered jacket top.

3.Place the inner stack adapter panel over the flue collector inside the heater. Make sure the flanged side of the flue opening is up.

4.Turn the stack (drafthood) upside down and set it down bottom side up.

5.Turn the jacket top panel (removed in step 1) upside down and place it through the stack.

6.Attach the three (3) mounting brackets to the stack using the screws provided and the holes that are pre-drilled in the stack. Make sure the brackets are positioned with the flange near the top side of the stack (see illustration 8246.5). Caution must be taken not to over tighten and strip the screw threads.

7.Turn the assembled stack and jacket top, right side up. The jacket top will be trapped between the brackets and the top of the stack. Place the stack over the inner adapter panel flanged hole and lower the louvered jacket top panel back into its original position. Reinstall the four (4) green #10 flathead screws removed in step 1 above.

Fig. # 8246.5

MODELS 514-824

Locate and assemble as shown below. Secure with screws supplied in envelope in carton.

Fig. # 8167

MODELS 962-1826

Locate and assemble as shown below. Secure with screws supplied in envelope in carton.

Fig. # 8165

MODELS 2100-4001

These models have built-in drafthoods. For proper operation, the drafthood outlet must be connected to the venting system.

13

Page 13
Image 13
Raypak 0133-4001 WH, NH manual Vent TERMINAL/INDOOR Stack Installation