Gas Fireplaces

Venting Arrangements - Horizontal

Terminations

This lightly shaded area of the diagram shows allowable combinations of vertical runs with horizontal terminations, using one 45° and one 90° elbow (two 45º elbows equal one 90° elbow).

Note: Must use optional rigid pipe adapter (Part # 510-994) when using Rigid Pipe.

P33 Gas Fireplace

Maintain clearances to combustibles.

Horizontal vent must be supported every 3 feet.

Firestops are required at each floor level and whenever passing through a wall.

A vent guard may be required as per local codes, refer to Exterior

Vent Termination Locations.

Note: FPI Direct Vent System (Flex) is only approved for horizontal terminations.

*Unit must be raised by 1” when using Contemporary Faceplate

Please refer to Exterior Vent Terminations for

additional guidelines on vent locations.

Gas Fireplaces

August 2008 Product Specifications Book

35

Page 8
Image 8
Regency 510-994, 946-523/P specifications Venting Arrangements Horizontal Terminations, Vent Termination Locations