Regency P131-NG, P121LC-NG, P121RC-NG, P121-NG Horizontal Flueing with Two 2 90o Elbows

Models: P121RC-NG P131-NG P121LC-NG P121-NG

1 40
Download 40 pages 42.51 Kb
Page 16
Image 16
Horizontal Flueing with Two (2) 90o Elbows

INSTALLATION

Horizontal Flueing with Two (2) 90o Elbows

Option

V

H + H1

A)

1' (305mm) Minimum

2' (610mm) Maximum

B)

2' (610mm) Minimum

5' (1.5m) Maximum

C)

3' (914mm) Minimum

8' (2.4m) Maximum

D)

4' (1.22m) Minimum

11' (3.35m) Maximum

E)

5' (1.5m) Minimum

14' (4.27m) Maximum

F)

6' (1.86m) Minimum

15' (4.5m) Maximum

With the above options, maximum total pipe length if 37 feet with minimum of 6 feet total vertical and maximum 15 feet total horizontal.

Please note minimum 1 foot between 90o elbows is required.

Horizontal Flueing with Three (3) 90o Elbows

Option

V

H

H + H1 + H2

A)2' (610mm) Min. 1' (305mm) Max. 3' (914mm) Max.

B)3' (914mm) Min. 3' (914mm) Max. 6' (1.86m) Max.

C)

4' (1.22mm) Min. 5'

(1.5m) Max.

9' (2.7m) Max.

D)

5' (1.5m) Min.

7'

(2.13m) Max.

12' (3.6m) Max.

With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.

Please note minimum 1 foot between 90o elbows is required.

Diagram 5

Diagram 3

Horizontal Flueing with Two (2) 90o Elbows

Option

V

H

H + H1

A)1' (305mm) Min. 1' (305mm) Max. 3' (914mm) Max.

B)2' (610mm) Min. 3' (0.91m) Max. 6' (1.86m) Max.

C)

3' (914mm) Min.

5' (1.5m) Max.

9' (2.7m) Max.

D)

5' (1.5m) Min.

8' (2.4m) Max.

12' (3.6m) Max.

With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.

Please note minimum 1 foot between 90o elbows is required.

Horizontal Flueing with Three (3) 90o Elbows

Option

 

V + V1

H + H1

A)

2' (610mm) Minimum

3' (914mm) Maximum

B)

3' (914mm) Minimum

6' (1.86m) Maximum

C)

4'

(1.22m) Minimum

9' (2.7m) Maximum

D)

5'

(1.5m) Minimum

12' (3.6m) Maximum

With the above options, maximum total pipe length if 37 feet with minimum of 5 feet total vertical and maximum 12 feet total horizontal.

Please note minimum 1 foot between 90o elbows is required.

Diagram 4

Diagram 6

 

 

16

Regency P121/P121LC/P121RC/P131 Zero Clearance Room Sealed Gas Fireplace

Page 16
Image 16
Regency P131-NG, P121LC-NG, P121RC-NG Horizontal Flueing with Two 2 90o Elbows, Horizontal Flueing with Three 3 90o Elbows