INSTALLATION

VERTICAL TERMINATION WITH

CO-LINEAR FLEX SYSTEM

THE APPLIANCE MUST NOT BE CONNECTED TO A CHIMNEY FLUE SERVING

A SEPARATE SOLID FUEL BURNING APPLIANCE.

This appliance is designed to be attached to two 3" (76mm) co-linear aluminium flex running the full length of the chimney. See the Venting Arrangements chart on page 10 for minimum and maximum flue lengths.See chart below for minimum distances from roof. Periodically check that the vent is unrestricted.

Masonry chimneys may take various contours which the flexible liner will accommodate. However, keep the flexible liner as straight as possible, avoid unnecessary bending.

The Air Intake pipe must be attached to the inlet air collar of the termination cap.

Required Parts:

Part # Description

946-529 Co-linear DV Vertical Termination Cap 948-305 3" Flex - 35 ft.

640-994 U37 Rigid Pipe Adaptor

946-563 Co-Axial to Co-Linear Adapter Kit which contains the following: Co-linear Flex Adapter (270-585) Outer Pipe (946-257)

Inner Pipe Adapter (946-219)

Alternate Approved Caps

 

Co-linear DV

 

980

Vertical Termination Cap

 

Vertical Termination

 

991

High Wind Cap

 

 

 

Cap # 946-529

 

923GK

3" Co-linear Adapter

 

 

 

 

 

 

with flashing

 

Check local

 

 

 

 

 

 

 

codes whether

 

 

 

 

a continuous

 

 

 

 

length is re-

 

 

 

 

quired or if

Flex Liner

 

 

certified joiner

 

 

 

 

kits may

 

 

 

 

be used.

 

 

 

 

#948-305

 

 

 

 

(35 ft)

 

 

 

 

Exhaust

 

 

 

 

Flue

 

U37 Rigid Pipe

Adaptor

Part # 640-994

Air Intake

 

Co-Linear

 

Flex

 

Adapter

 

with Kit#

 

946-563

Inner Pipe

 

Adapter

Outer

with Kit#

946-563

Pipe

 

with Kit#

 

946-563

U37 Regency ULTIMATE Rear Vent Direct Vent Freestanding Gas Heater

13

Page 13
Image 13
Regency U37-NG NATURAL GAS, U37-LP PROPANE Vertical Termination with CO-LINEAR Flex System, Required Parts Description