INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS

Commonwealth of Massachusetts

For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

INSTALLATION OF CARBON MONOXIDE DETECTORS

At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gasfitter shall

observe that a hard wired carbon monoxide detector with an

alarm and battery back-up is installed on the floor level where

the gas equipment is to be installed. In addition, the installing

plumber or gasfitter shall observe that a battery operated or

hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the

services of qualified licensed professionals for the installation of

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may

be installed on the next adjacent floor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

APPROVED CARBON MONOXIDE DETECTORS

Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/ UL 2034 listed and CSA certified.

SIGNAGE

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one- half (1/2) inch in size, “gas vent directly below. Keep clear of all obstructions.”

Inspection

The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled “Equipment Not

Required To Be Vented” in the most current edition of NFPA

54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1.Detailed instructions for the installation of the venting system design or the venting system components; and

2.A complete parts list for the venting system design or venting system.

MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems,” the following requirements shall be satisfied by the manufacturer:

1.The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

2.The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

6

Page 6
Image 6
Reliance Water Heaters 6 50YTVIT SERIES 100 Installation of Carbon Monoxide Detectors, Approved Carbon Monoxide Detectors

317686-000, 6 50YTVIT SERIES 100 specifications

The Reliance Water Heaters 6 50YTVIT Series is a top-performing line of electric water heaters designed to deliver reliable hot water for residential needs. This model, identified by the part number 100,317686-000, showcases exceptional efficiency and innovative features that make it a popular choice among homeowners.

One of the standout characteristics of the 6 50YTVIT is its 50-gallon capacity, providing ample hot water to meet the demands of larger households. The tank is constructed from durable materials to ensure longevity, featuring a glass-lined interior that helps resist corrosion, extending the lifespan of the unit.

An important feature of this water heater is its energy efficiency. It is built with a high-efficiency heating element that reduces energy consumption, ultimately leading to lower utility bills. The unit also has an ENERGY STARĀ® certification, indicating it meets strict energy efficiency guidelines set by the Environmental Protection Agency. This makes it not only an eco-friendly choice but also a cost-effective one.

The Reliance 6 50YTVIT is equipped with advanced safety mechanisms, including a combination temperature and pressure relief valve, which protects the unit from overheating or excessive pressure build-up. This ensures safe operation, providing peace of mind for users.

Installation and maintenance are made easier with the thoughtful design of this water heater. Its lightweight construction facilitates hassle-free handling and installation, even in tighter spaces. Additionally, the unit is designed for easy access to the heating elements for maintenance, helping to reduce downtime and cost.

Technologically, this water heater adopts a versatile voltage system, making it compatible with a wide range of electrical supplies. It can operate effectively in various home settings, enhancing its adaptability.

In conclusion, the Reliance Water Heaters 6 50YTVIT Series 100,317686-000 stands out for its robust capacity, energy efficiency, and safety features. Its dependable performance and ease of maintenance make it an ideal choice for homeowners looking for a reliable water heating solution that ensures comfort and convenience in daily life. With its thoughtful design and competitive features, the Reliance 6 50YTVIT series continues to be a preferred selection in modern home water heating applications.