barb, use a wire tie or hose clamp (not supplied with kit) and secure.

6.Take the other end of the flexible tubing and slide it through the hose clamp on the jacket top cover and install it into one of the four barb fittings in vent pipe assembly #2.

7.Once installed along with the rest of the vent configuration, make sure to operate the unit through at least one heat up cycle to ensure there is no leakage around the hose barb or any joints of the VAA or vent pipe system.

FIGURE 23: Typical Horizontal Installation

Installation for VAA with 3 & 4 inch Pipe for Vertical Vent

Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths. Please refer to Figure 24 as you review these instructions. Refer back to the vertical VAA installation steps but with the following changes to the vent construction.

3 inch vent (Vertical VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA, a short run of 2 inch vent pipe is required. Each of the short pieces of 2 inch pipe entering and exiting the VAA must not exceed 6 inches (15 cm) in length. From this point on, a 2 inch to 3 inch adapter may be used. From the 2 inch to 3 inch adapter, the installer may use up to 65 equivalent feet (19.8 m) of pipe, see Figure 24 for typical installation.

4 inch vent (Vertical VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA, a short run of 2 inch vent pipe is required. Each of the short pieces of 2 inch pipe entering and exiting the VAA must not exceed 6 inches (15 cm) in length. From this point on, a 2 inch to 4 inch adapter may be used. From the 2 inch to 4 inch adapter, the installer may use up to 128 equivalent feet (39.0 m) of pipe, see Figure 24 for typical installation.

Remember to operate the unit for at least one heat cycle to ensure there are no air leaks in the vent joints of the VAA and the vent pipe system. Air leaks will allow flue gas by-products to disseminate into the room creating an unsafe environment and could cause illness, asphyxiation and/or even death.

FIGURE 24: Typical Installation for Vertical Vent with 3 or 4 inch Pipe

Installation of VAA with 3 & 4 inch Pipe for Horizontal Vent Some applications may require the use of 3 or 4 inch vent pipe for longer vent lengths. Please refer to the Figure 25 as you review these instructions. Refer back to the horizontal VAA installation steps but with the following changes to the vent construction.

3 inch vent (Horizontal VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between blower assembly and inlet into the VAA. On the outlet side of the VAA, a short run of 2 inch vent pipe is required. From this point on, a 2 inch to 3 inch adapter may be used. From the 2 inch to 3 inch adapter, installer may use up to 52 equivalent feet (15.8 m) of pipe. This is 8 equivalent feet (2.4 m) less than the original 60 equivalent feet (18.3 m) specified with one elbow due to the 2 inch elbow instead of a 3 inch elbow required for vent from blower to the inlet of VAA, see Figure 25 for typical installation.

4 inch vent (Horizontal VAA Installations)

The VAA is designed to accommodate only 2 inch vent pipe. The installer must use 2 inch vent pipe between the blower assembly and the inlet into the VAA. On the outlet side of the VAA a short run of 2 inch vent pipe is required. From this point on, a 2 inch to 4 inch adapter may be used. From the 2 inch to 4 inch adapter, the installer may use up to 102 equivalent feet (31.1 m) of pipe. This is 18 equivalent feet (5.5 m) less than the original 120 equivalent feet (36.6 m) specified with one elbow due to the 2 inch elbow instead of a 4 inch elbow required for the vent from the blower to the inlet of the VAA, see Figure 25 for typical installation.

Remember to operate the unit for at least one heat cycle to ensure there are no air leaks in the vent joints of the VAA and the vent pipe system. Air leaks will allow flue gas by-products to disseminate into the room creating an unsafe environment and could cause illness, asphyxiation and/or even death.

FIGURE 25: Typical Installation for Horizontal Vent with 3 or 4 inch Pipe

25

Page 25
Image 25
Reliance Water Heaters 317686-000, 6 50YTVIT SERIES 100 instruction manual Inch vent Vertical VAA Installations

317686-000, 6 50YTVIT SERIES 100 specifications

The Reliance Water Heaters 6 50YTVIT Series is a top-performing line of electric water heaters designed to deliver reliable hot water for residential needs. This model, identified by the part number 100,317686-000, showcases exceptional efficiency and innovative features that make it a popular choice among homeowners.

One of the standout characteristics of the 6 50YTVIT is its 50-gallon capacity, providing ample hot water to meet the demands of larger households. The tank is constructed from durable materials to ensure longevity, featuring a glass-lined interior that helps resist corrosion, extending the lifespan of the unit.

An important feature of this water heater is its energy efficiency. It is built with a high-efficiency heating element that reduces energy consumption, ultimately leading to lower utility bills. The unit also has an ENERGY STARĀ® certification, indicating it meets strict energy efficiency guidelines set by the Environmental Protection Agency. This makes it not only an eco-friendly choice but also a cost-effective one.

The Reliance 6 50YTVIT is equipped with advanced safety mechanisms, including a combination temperature and pressure relief valve, which protects the unit from overheating or excessive pressure build-up. This ensures safe operation, providing peace of mind for users.

Installation and maintenance are made easier with the thoughtful design of this water heater. Its lightweight construction facilitates hassle-free handling and installation, even in tighter spaces. Additionally, the unit is designed for easy access to the heating elements for maintenance, helping to reduce downtime and cost.

Technologically, this water heater adopts a versatile voltage system, making it compatible with a wide range of electrical supplies. It can operate effectively in various home settings, enhancing its adaptability.

In conclusion, the Reliance Water Heaters 6 50YTVIT Series 100,317686-000 stands out for its robust capacity, energy efficiency, and safety features. Its dependable performance and ease of maintenance make it an ideal choice for homeowners looking for a reliable water heating solution that ensures comfort and convenience in daily life. With its thoughtful design and competitive features, the Reliance 6 50YTVIT series continues to be a preferred selection in modern home water heating applications.