Reliance Water Heaters 317686-000 Sediment Traps, Filling the Water Heater, Gas Piping With All

Models: 317686-000 6 50YTVIT SERIES 100

1 40
Download 40 pages 10.09 Kb
Page 17
Image 17
SEDIMENT TRAPS

A gas line of sufficient size must be run to the water heater.

Consult the current edition of National Fuel Gas Code (ANSI Z223.1/NFPA 54) and your gas supplier concerning pipe size.

There must be:

A readily accessible manual shuttoff valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of gas control valve to help prevent dirt and foreign materials from entering the gas control valve.

A flexible gas connector or a ground joint union between the shuttoff valve and control valve to permit servicing of the unit.

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a match or open flame. Rinse off soapy solution and wipe dry.

Use pipe joint compound or teflon tape marked as being resistant to the action of petroleum [Propane (L.P.)] gases.

The appliance and its gas connection must be leak tested before placing the appliance in operation.

The appliance and its individual Shuttoff valve should be disconnected from the gas supply piping system during any pressure testing of that

system at test pressures in excess of 1/2 pound per square inch (3.5 kPa).

It should be isolated from the gas supply piping system by closing its individual manual Shuttoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 pound

per square inch (3.5 kPa).

Connecting gas piping to the gas control valve of water heater can be accomplished by either of two methods shown in Figures 12 and 13.

SEDIMENT TRAPS

A sediment trap should be installed as close to the inlet of the water heater as practical at the time of water heater installation. The sediment trap should be either a tee fitting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap. If a tee fitting is used, it should be installed in conformance with one of the methods of installation shown in Figures 12 and 13.

Contaminants in the gas lines may cause improper operation of the gas control valve that may result in fire or explosion. Before attaching the gas line be sure that all gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a drip leg (sometimes called a sediment trap) must be incorporated in the piping. The drip leg must be readily accessible. Install in accordance with the “Gas Piping” section. Refer to the current edition of the National Fuel Gas Code (ANSI Z223.1/NFPA 54).

FIGURE 12. GAS PIPING WITH

FLEXIBLE CONNECTOR.

FIGURE 14.

Filling the Water Heater

FIGURE 13. GAS PIPING WITH ALL

BLACK IRON PIPE TO GAS CONTROL.

17

Page 17
Image 17
Reliance Water Heaters 317686-000 Sediment Traps, Filling the Water Heater, Gas Piping With Flexible Connector