Check Venting

The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation.

1.Seal any unused openings in the venting system.

2.Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1or the CAN/CGA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

3.So far as is practical, close all building doors and windows and all doors between the space in which the water heater(s) connected to the venting system are located and other spaces of the building. Turn on all appliances not connected to the venting system. Turn on all exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Close fireplace dampers.

4.Follow the lighting instruction. Place the water heater being inspected in operation. Adjust thermostat so appliance shall operate continuously.

5.Test for spillage at the burner level after 5 minutes of main burner operation.

6.After it has been determined that each water heater connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

7.If improper venting is observed during any of the above tests, the venting system must be corrected.

FAILURE TO CORRECT BACK DRAFTS MAY CAUSE AIR CONTAMINATION AND UNSAFE CONDITIONS.

If the back draft cannot be corrected by the normal method or if a suitable draft cannot be obtained, a blower type flue gas exhauster must be employed to assure proper venting and correct combustion.

Check the Igniter Assembly

At least once a year, check the igniter assembly, Figure 23, and the main burner, Figure 24, for proper operation. Refer to the

following igniter assembly and main burner sections.

FIGURE 23

Main Burner

The main burner, figure 24, should display the following characteristics:

Cause rapid ignition and carry across entire burner.

Give reasonably quiet operation during ignition, burning, and extinction.

Cause no excessive lifting of flame from burner ports.

FIGURE 24

If the preceding burner characteristics are not evident, check for accumulation of lint, scale or other foreign debris that restricts or blocks the air openings to the burner or heater.

NOTE:

1.Remove main burners from unit.

2.Check that burner venturi and ports are free of foreign debris.

3.Clean burners with bristle brush and/or vacuum cleaner - DO NOT distort burner ports or pilot location.

4.Reinstall burners in unit. Make sure front and rear of burners are installed correctly in burner support brackets.

Also check for good flow of combustion and ventilating air to the unit. Maintain a clear area around the heater at all times.

Gas Valves

Figure 25 shows the type of combination manual gas control valve and regulator used on these heaters.

If the gas valve becomes defective, repairs should not be attempted. A new valve should be installed in place of the defective one.

Igniter Assembly

For access to igniter assembly, unfasten two screws to burner cover and remove. Locate the burner with the igniter assembly and remove screw holding burner to manifold. Slide burner out to access igniter assembly.

Servicing of the igniter assembly includes keeping the igniter free

 

of lint, scale or any other foreign debris.

FIGURE 25

25

Page 25
Image 25
Reliance Water Heaters D85500PE, D85500NE Check Venting, Check the Igniter Assembly, Main Burner, Gas Valves

D85500PE, D85500NE specifications

Reliance Water Heaters offers a diverse range of high-performance water heaters, with the D85500NE and D85500PE models standing out for their exceptional features and innovative technologies. Designed to meet the needs of modern households, these water heaters are engineered for efficiency, reliability, and ease of use.

The D85500NE is a natural gas water heater that boasts a 50-gallon capacity, making it an excellent choice for medium to large households. One of its main features is the Energy Factor (EF) rating, which ensures efficient operation and reduces energy costs. With a recovery rate of approximately 41 gallons per hour, it's capable of delivering a steady supply of hot water without delays, ensuring that families can enjoy uninterrupted use during peak demands.

The D85500PE model, on the other hand, operates using propane, catering to households with propane systems. Like its natural gas counterpart, the D85500PE also has a 50-gallon capacity and delivers a comparable recovery rate. Both models feature a glass-lined tank, providing corrosion resistance and extending the lifespan of the water heater. This protective lining is crucial for maintaining water quality and ensuring durability over time.

In terms of technology, both the D85500NE and D85500PE are equipped with advanced thermostat and burner systems that allow for precise temperature control. The integrated piezo ignition allows for easy start-up, enabling users to ignite the burner with a simple push of a button. Additionally, the water heaters are designed with safety features such as a pressure relief valve, which prevents excessive pressure build-up.

Another notable characteristic of these models is their user-friendly accessibility. Maintenance access is made simple with installation features that enable straightforward servicing and repairs. The compact design of the units also allows for versatile installation options, whether in a basement, garage, or utility closet.

Finally, both the D85500NE and D85500PE are backed by a solid warranty, providing peace of mind for consumers. With their combination of efficiency, reliability, and advanced features, these water heaters from Reliance Water Heaters are an outstanding choice for anyone looking to enhance their home’s hot water system.