b. WATER
Water piping should be installed according to the local code requirements, ASHRAE, ASPE and BOCA or other regulatory agencies.
COLD WATER SUPPLY
The cold water supply piping, to the heater must be adequate to handle the design load requirements of the hot water system. The following table illustrates the flow and minimum pipe sizes.
|
|
|
|
|
|
|
|
|
|
|
|
| Min |
|
| Min |
|
| Min |
| Model | Flow | Pipe | Model | Flow | Pipe | Model | Flow | Pipe |
| Size | GPM | NPT | Size | GPM | NPT | Size | GPM | NPT |
136 | 22 | 825 | 85 | 2 | 1413 | 90 | |||
181 | 30 | 926 | 90 | 1467 | 90 | ||||
| 264 | 42 | 962 | 90 | 1570 | 90 | |||
331 | 53 | 1083 | 90 | 1630 | 90 | ||||
| 399 | 63 | 1125 | 90 | 1758 | 90 | |||
| 512 | 82 | 2 | 1178 | 90 | 1826 | 90 | ||
| 627 | 85 | 2 | 1287 | 90 |
|
|
| |
726 | 85 | 2 | 1337 | 90 |
|
|
|
It is recommended that a gate valve be installed in the cold water supply line adjacent to the heater. If Local Codes require a check valve - provisions must be made for thermal expansion.
A minimum pressure of 30 PSIG must be maintained in the system to prevent damage to the heater due to lack of water circulation caused by vapor formation at suction side of the system pumps.
NOTE: Should the cold water supply be interrupted, for any reason, the gas supply must be manually shut off to prevent heater damage. When the service is restored the lines must be vented to eliminate accumulated air.
20