Rheem 136-1826 installation instructions

Models: 136-1826

1 55
Download 55 pages 51.92 Kb
Page 14
Image 14
14
Fig # 8119
HEATER
DRAFT HOOD
VENT PIPE
5' MIN
2' MIN
2' MIN
VENT CAP
10' OR LESS
Vent piping the same size or larger than the draft hood outlet is recommended, however, when the total vent height is at least ten (10) feet (draft hood relief opening to vent terminal), the vent pipe size may be reduced as specified in Chapter 10 of the National Fuel Gas Code, ANSI Z223.1. As much as possible avoid long horizontal runs of vent pipe and too many elbows. If installation requires horizontal non-vertical runs, the vent pipe must have a minimum of 1/4 inch per foot rise and should be supported at not less than five foot intervals. Plumbers tape, criss-crossed, will serve to space both horizontal and vertical piping. Gas vents supported only by the flashing and extending above the roof more than five feet should be securely guyed or braced to withstand snow and wind load. We recommend use of insulated vent pipe must terminate with a vent cap which complies with the local codes or, in the absence of such codes, to the latest edition of the National Fuel Gas Code, ANSI Z223.1.
The discharge opening must be a minimum of three feet vertically from the roof surface and at least two feet higher than any
part of the building within ten feet. Vent stack shall be at least five feet in vertical height above the drafthood outlet. The vent cap location shall have a minimum clearance of 4 feet horizontally from,
and in no case above or below, unless a 4-foot horizontal distance
is maintained, from electric meters, gas meters regulators and relief
equipment. The weight of the vent stack or chimney must not rest on the
heater draft hood. Support must be provided in compliance with
applicable codes. The heater top and draft hood must be readily removable for maintenance and inspection. Vent pipe should be
adequately supported to maintain proper clearances from combus- tible construction.
Type "B" double wall or equivalent vent pipe is recommended.
However single wall metal vent pipe may be used as specified in the latest edition of the National Flue Gas Code ANSI Z223.1.
MODELS 962 - 1826
Locate and assemble as shown below. Secure with screws supplied in envelope in carton.
Fig. #8265.0
WARNING:
Indoor heaters require a drafthood that must be connected to a vent pipe and properly vented to the outside. Failure to follow this procedure can cause fire or fatal carbon monoxide poisoning.
Page 14
Image 14
Rheem 136-1826 installation instructions

136-1826 specifications

The Rheem 136-1826 is a highly efficient heating and cooling unit designed to provide reliable performance and comfort in residential settings. This unit is particularly notable for its advanced features, robust technologies, and outstanding characteristics that set it apart in the HVAC market.

One of the defining features of the Rheem 136-1826 is its energy efficiency. Rated with a high Seasonal Energy Efficiency Ratio (SEER), this unit efficiently converts energy into cooling output, leading to significant savings on utility bills. The environmentally friendly refrigerants used in its operation comply with current global regulations and aim to minimize any negative impact on the ozone layer.

Additionally, the Rheem 136-1826 incorporates advanced climate control technologies. Its innovative multi-stage compression offers superior cooling performance and an enhanced ability to maintain comfortable temperatures, even during extreme weather conditions. The variable-speed motor allows for precise airflow management, leading to quieter operation and improved indoor air quality by minimizing dust and allergens in circulation.

Another remarkable attribute of the Rheem 136-1826 is its smart technology integration. Homeowners can connect the unit to Wi-Fi and control it remotely through a mobile app. This feature not only provides convenience but also allows users to monitor system performance, adjust settings, and receive maintenance reminders. The programmable thermostat included in the setup further enhances energy conservation efforts, enabling users to tailor their heating and cooling schedules to their lifestyle.

In terms of installation and maintenance, the Rheem 136-1826 has been designed with user-friendliness in mind. Its compact size allows for easy installation in various locations, making it a versatile choice for different home designs. The durable construction materials used in this unit ensure longevity and reduced maintenance needs over time.

Overall, the Rheem 136-1826 stands out for its combination of energy efficiency, advanced cooling technologies, smart features, and ease of use. It is an ideal choice for homeowners looking for a reliable and efficient heating and cooling solution that not only enhances indoor comfort but also contributes to long-term energy savings. Whether replacing an old system or installing a new one, the Rheem 136-1826 is well-equipped to meet the demands of modern living.