“System Sentinel”Troubleshooting Guide

Section 4... the “PILOT VALVE” LED

NO

 

Is the“PILOT VALVE”LED Illuminated?

YES

Is the Spark Ignitor operating?

 

 

 

 

The Ignition Control Module is in

YES

 

Is the Pilot Flame burning?

the Ignition sequence, and is pro-

(Can sparking be heard?)

 

 

 

 

 

viding 24 VAC power to the ECO

 

 

 

 

 

 

 

 

YES

NO

(Energy Cut-Off Device) inside of

 

 

 

theThermostat

NO

The System Sentinel Panel is defective and must be replaced.

1. Remove Ignition Cable and check for good conti-

 

 

 

 

 

 

 

 

 

 

nuity, replace if necessary.

 

 

 

 

 

 

 

 

 

 

2. Check Ignitor Electrode gap for proper spacing

 

 

 

 

 

 

 

 

 

 

(1/8”to 5/32”). Correct if necessary.

 

Is 24 VAC present between the Brown

wire on “PV”

 

YES

3. Examine Ceramic

Insulator on Pilot Assembly

YES

Terminal and White wire on “PV/MV”

Terminal on

 

 

for cracks. Replace if cracks are evident.

 

the Gas ControlValve?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is 24 VAC present between the Brown wire on “PV”

 

 

 

 

 

 

 

 

 

 

Terminal and Gray Ground wire on Ignition Control

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

Module?

 

 

 

 

NO

 

I

s

 

 

 

 

 

 

 

 

 

 

the inlet gas pres-

 

 

 

 

 

 

 

 

 

 

sure at or below the

 

 

 

 

 

 

Gas Control Valve

maximum as speci-

 

 

 

 

 

 

fied on the rating

 

 

 

 

 

 

is inoperable and must

plate?

 

NO

 

 

be replaced

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is the“IGNITION”LED illuminated?

 

Is the “ECO” LED

 

 

 

 

 

 

 

 

 

 

 

 

illuminated?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

NO

 

 

YES

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check continuity of Brown wire

 

 

 

 

 

 

 

 

 

 

 

between ECO Device (inside of Ther-

 

 

 

 

 

 

 

Ignition

Control Module

 

mostat), and “PV” Terminal on Gas

 

 

 

 

 

 

 

is inoperable and must be

 

ControlValve. Repair or replace wire as

 

 

 

 

 

 

 

replaced.

 

 

 

needed to restore power to “PV”Termi-

 

 

 

 

 

 

 

 

 

 

 

nal on gas valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to Section 3...the“IGNI-

 

Refer to Section 5...the“ECO”LED in

 

 

 

 

 

TION”LED in theTroubleshooting Guide

 

theTroubleshooting Guide

 

 

 

 

!CAUTION

Label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERIFY PROP-

ER OPERATION AFTER SERVICING!