Rheem Commercial Power Direct Vent Water heater System SentinelTroubleshooting Guide, Power Led

Models: Commercial Power Direct Vent Water heater

1 28
Download 28 pages 32.61 Kb
Page 20
Image 20

“System Sentinel”Troubleshooting Guide

Section 1... the “POWER” LED

NO

Is the“ON/OFF”Switch in the “ON”position?

YES

Is the“POWER”LED Illuminated?

YES

NO

Turn switch to ON position. Is the

YES

Power is

Power LED now illuminated?

being supplied to the heater,

 

 

 

 

 

 

 

the ON/OFF Switch is func-

 

 

 

 

tioning, and the 24V AC

 

 

 

 

Transformer is functioning.

NO

Is 120 VAC power present at the

NO

Check circuit breaker or fuse and field connec-

 

branch circuit connections to Black

tion of branch circuit wiring to leads of switch.

YES

 

 

 

Repair or replace as required. Is “POWER” LED

wire of the switch and White wire of

 

 

 

the transformer ?

 

now illuminated?

 

YES

 

 

NO

 

 

 

 

 

 

 

 

Replace Switch, then verify that

 

Is 120 VAC power present between

 

 

the Black and White wires to the

NO

power is present. Is “POWER” LED

YES

transformer ?

 

now illuminated?

 

 

 

 

 

 

 

NO

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace Transformer, then verify

 

 

 

 

 

 

 

Is 24 VAC power present between

NO

 

the Yellow and Gray wires from the

 

that power is present. Is “POWER”

YES

transformer

?

 

 

 

LED now illuminated?

 

 

 

 

 

 

 

 

 

 

YES

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The System Senti-

 

 

 

 

 

nel Panel is defective and must be

 

 

 

 

 

replaced.

 

 

 

 

 

!CAUTION

Label all wires prior to disconnection when servicing controls.Wiring errors can cause improper and dangerous operation. VERIFY PROP-

ER OPERATION AFTER SERVICING!