Rheem Commercial Power Direct Vent Water heater Installation Check List, For Proper Installation

Models: Commercial Power Direct Vent Water heater

1 28
Download 28 pages 32.61 Kb
Page 13
Image 13

FOR PROPER INSTALLATION:

!CAUTION

DO NOT use solvent cement that has become curdled, lumpy or thickened.

DO NOT thin solvent cement. Observe shelf precautions printed on the containers.

For applications below 32°F use only low temperature type solvent cement.

Appropriate solvent and cleaner must be used for the type of vent pipe used (PVC, CPVC or ABS).

Avoid skin or eye contact. Observe all cautions and warnings on material containers.

6.WIRING — A polarized 120V 50/60 Hz power supply, with suitable disconnect means, must be connected to the black and white leads provided. The current draw by the Power Direct Vent unit is 1.5 Amps. The water heater, when installed, must be electrically grounded in ac- cordance with local codes, or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70 in the United States; or CSA C22.1 Electrical Code, in Canada. Refer to Fig. 14 on page 26 & 27 of this manual for water heater internal wiring diagrams.

NOTICE: DO NOT use in conjunction with a GFCI.

!WARNING

DANGER OF FIRE OR BODILY INJURY – Solvent cements and primers are highly flammable. Pro- vide adequate ventilation and do not assemble near heat source or open flame. Do not smoke.

Installation Check List

A.Water Heater Location

Close to area of vent.

Indoors and protected from freezing temperatures.

Proper clearance from combustible surfaces observed and water heater not installed on carpeted floor.

Air supply free of corrosive elements and flammable vapors.

Provisions made to protect area from water damage.

Sufficient room to service heater.

B.Water Supply

Water heater completely filled with water.

Water heater and piping air vented.

Water connections tight and free of leaks.

C.Gas Supply

Gas line equipped with shut-off valve, union, and sediment trap/drip leg.

Approved pipe joint compound used.

Soap and water solution used to check all connections and fittings for possible gas leak.

Gas Company inspected installation (if required).

D.Relief Valve

Discharge line run to open drain.

Discharge line protected from freezing.

E.Venting

All pipe connections are secure (at blower, vent terminals and for each pipe joint connection)

Vent terminals mounted properly and in correct location.

Condensate tube has water in both loops.

TABLE 1

Maximum Capacity of Pipe in Cubic Feet of Gas per Hour for Gas Pressures of

‑‑‑‑‑‑‑‑0.5 psig or Less and a Pressure Drop of 0.3 Inch Water Column

Based on a 0.60 Specific Gravity Natural Gas; If 1.5 Specific Gravity L.P. Gas is used, multiply capacity by 0.63

Nominal

Internal

 

 

 

 

 

Length of Pipe, Feet

 

 

 

 

 

 

Iron Pipe Size,

Diameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inches

Inches

10

20

30

40

50

60

70

80

 

90

100

125

150

175

200

1/2

.622

132

92

73

63

56

50

46

43

 

40

38

34

31

28

26

3/4

.824

278

190

152

130

115

105

96

90

 

84

79

72

64

59

55

1

1.049

520

350

285

245

215

195

180

170

 

160

150

130

120

110

100

1 1/4

1.380

1,050

730

590

500

440

400

370

350

 

320

305

275

250

225

210

1 1/2

1.610

1,600

1,100

890

760

670

610

560

530

 

490

460

410

380

350

320

2

2.067

3,050

2,100

1,650

1,450

1,270

1,150

1,050

990

 

930

870

780

710

650

610

2 1/2

2.469

4,800

3,300

2,700

2,300

2,000

1,850

1,700

1,600

 

1,500

1,400

1,250

1,130

1,050

980

3

3.068

8,500

5,900

4,700

4,100

3,600

3,250

3,000

2,800

 

2,600

2,500

2,200

2,000

1,850

1,700

4

4.026

17,500

12,000

9,700

8,300

7,400

6,800

6,200

5,800

 

5,400

5,100

4,500

4,100

3,800

3,500

13

Page 13
Image 13
Rheem Commercial Power Direct Vent Water heater installation instructions Installation Check List, For Proper Installation

Commercial Power Direct Vent Water heater specifications

The Rheem Commercial Power Direct Vent Water Heater is engineered to meet the demanding needs of commercial applications, providing reliable and efficient hot water for various business environments. With a focus on performance, efficiency, and durability, this water heater stands out in the competitive landscape of commercial water heating solutions.

One of the key features of the Rheem Commercial Power Direct Vent Water Heater is its direct vent capability. This innovative design allows for installation in confined spaces while optimizing exhaust methods. The direct vent system enables the heater to draw air from outside the building for combustion, ensuring safe operation, reducing risk of backdraft, and maintaining indoor air quality.

The water heater is powered by either natural gas or propane, accommodating diverse fuel supply preferences. With a range of storage capacities, it can cater to small and large businesses, from restaurants to industrial facilities. The product’s high recovery rate ensures that it can meet peak hot water demands, making it an ideal solution for facilities with fluctuating hot water usage.

Equipped with advanced technology, the Rheem Commercial Power Direct Vent Water Heater features a state-of-the-art electronic control system that allows for easy temperature adjustments and monitoring. This interface ensures precise temperature control, so businesses can consistently deliver hot water at the required temperatures.

Durability is a hallmark of this water heater, which incorporates premium-grade components and materials. The tank is constructed with a glass-lined steel design that enhances resistance to corrosion, while also supporting longevity. Additionally, it features robust insulation that reduces heat loss, improving energy efficiency and lowering operating costs.

Another notable characteristic is the inclusion of a high-efficiency burner that maximizes fuel utilization, promoting energy savings and reducing emissions. The heater also complies with various energy standards, making it a sustainable choice for environmentally conscious businesses.

Installation and maintenance are streamlined with the Rheem Commercial Power Direct Vent Water Heater. Its compact design and versatile venting options allow for flexible placement. Furthermore, the unit is designed for easier access to critical components, making routine service and maintenance uncomplicated.

Overall, the Rheem Commercial Power Direct Vent Water Heater represents a fusion of efficiency, ease of use, and advanced technology, making it a smart investment for commercial establishments needing reliable hot water solutions. Whether in kitchens, manufacturing plants, or commercial offices, this water heater is engineered to deliver performance and peace of mind.