Installing the water heater.

The water heater must be installed with a RTG20002B vent adapter or a UL approved Category III Stainless Steel equivalent.

Venting

DANGER: Failure to install the vent adapter and properly vent the water heater to the outdoors as outlined in the Venting section of this manual will result in unsafe operation of the water heater causing death, serious injury, explosion, or fire. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, NEVER operate the water heater unless it is properly vented and has adequate air supply for proper operation as outlined in the Venting section of this manual.

The installation of venting must comply with national codes, local codes, and the vent manufacturer's instructions

The water heater must be vented to the outdoors as described in these instructions. DO NOT connect this water heater to an existing Vent or Chimney, it must be vented separately from all other appliances.

All vent components (adapters, pipe, elbows, terminals, etc.) should be UL1738 Certified Stainless Steel Venting Material (e.g. AL29-4C).

The specified vent termination must be used. The termination should be a 90° elbow type with screen. (Refer to page 15)

Follow vent manufacturer's installation instructions.

The unit can be vented either horizontally or vertically.

Vent pipe runs must be adequately supported along both horizontal and vertical runs.

The maximum recommended unsupported span should be no more than five (5) feet. Support isolation hanging bands should be used. DO NOT use wire. (See diagram below).

WARNING: Use UL

 

 

 

approved Category III

Use a vent pipe with an anti-disconnection

 

 

Stainless Steel vent material structure.

 

 

only. No other vent

 

 

 

material is permitted.

The use of a High Temperature Silicone

 

 

 

 

 

 

(500oF) may be required to seal vent

 

 

WARNING: Refer to

connections. To prevent accidental gas

 

 

exhaust leakage, apply a 1/4 wide bead

 

 

page 7 for clearances to

 

 

combustible material.

approximately 1/4 from the end and

 

 

 

another bead against the joint side of the

 

 

 

stop bead.

 

 

 

 

 

 

 

Venting Lengths

The vent can be installed with a slight

 

MAXIMUM VENT LENGTH - The

downward slope of 1/4 per foot of

 

horizontal run toward the vent terminal

 

system will not operate if there is

 

(see diagram below). This ensures that

 

excessive restriction (pressure drop) in the

 

any condensate formed during operation

 

venting system. A maximum of 47 feet 6

of the unit is evacuated from the

 

inches of vent pipe may be used provided

 

appliance.

 

there is only one 90o elbow in the system.

 

If additional elbows are required: two

A 1/4 per foot upward slope is acceptable

 

elbows can be used with 42 feet 6 inches,

 

when it is not possible to vent with a

 

and three elbows can be used with 37 feet

 

downward slope, however, a UL approved

 

6 inches of vent pipe.

 

Category III Stainless Steel condensate

 

 

 

A 90o elbow is equivalent to 5 feet to

trap MUST be installed at the beginning

 

 

of the horizontal run (See page 15

straight pipe. A 45o elbow is equivalent to

Typical Horizontal Termination

2 feet 6 inches of straight pipe.

w/ 1/4 per foot UPWARD Slope or

 

The termination elbow does not count as

page 16, Standard Vertical Vent

Termination for examples).

an elbow when determining total vent

 

lengths.

MINIMUM VENT LENGTH - The

 

 

venting may be as short as 12 , provided

 

one vent termination is installed to the

 

outdoors through a sidewall, one 90o

 

elbow is included in the installation, and

 

the wall thimble is installed.

 

Notice: Make sure that the seam of the

 

vent pipe in horizontal runs is toward the

 

top of the installation (see illustration to

 

the far left).

12

Page 12
Image 12
Rheem Residential Indoor Gas Tankless Water Heater Venting Lengths, Maximum Vent Length, Minimum Vent Length