Normal Operating Sequence

Adjust Gas Pressure Settings

6.Press the test switch twice to record the gas type code into memory. .

7.Press the ON/OFF button to operate the appliance.

8.Press the test switch twice. The LED will display “PL”.

9.Compare the pressure reading on the manometer to the desired manifold test pressure (low) for your gas type and altitude. If necessary adjust the low fire pressure using the ▲ and ▼ buttons.

10.Press the test switch. The LED will display “PH” indicating high fire mode.

11.Compare the pressure reading on the manometer to the desired manifold test pressure (high) for your gas type and altitude. If necessary adjust the high fire pressure using the ▲ and ▼ buttons.

12.Press the ON/OFF button again. The LED display turns blank and the appliance returns to the normal OFF mode.

13.Remove manometer and install Allen head screws. Operate the unit and

check the normal operating sequence

visually inspect the flame

check for gas leaks at the test points

Normal Operating Sequence

When you press the ON/OFF button, the LED display will illuminate, the combustion fan will begin to run, and the spark will ignite the main burner.

This heater has an automatic ignition system. When the main burner has lit, the combustion lamp will glow red, and the spark will stop.

Visual Inspection of Flame

Check that the burner flames are operating normally. The flame can be seen through the circular window through the louvers.

When operating normally the burner flame should appear as long, clear, blue, stable, streaks. Yellow flames or an orange color is abnormal and maintenance is required.

NORMAL

Flame Rod

Long, clear, blue, stable flames

ABNORMAL

Flame Rod Final Assembly

Yellow flames orManual background orange color

Final Assembly

1.Install the front panel and bottom cover.

2.If doing a gas type conversion, place the new conversion plate (label) on the front cover.