Optional Piping for Circulation Systems

Optional Piping for Circulation Systems

PLEASE NOTE THIS PIPING

ARRANGEMENT REDUCES

RESIDENTIAL AND COMMERCIAL

WARRANTY TO THE FOLLOWING:

3 Years On Heat Exchanger

3 Years On Parts

(Full warranty will be maintained if an on-demand recirculation system is incorporated.

Refer to the Limited Warranty.)

For this application:

Pump should be controlled by an Aquastat, Timer or Combination Aquastat and Timer.

Pump to be sized to maintain circulation loop temperature.

A minimum of 3 GPM flow is recommended for the circulation system.

The pump should be sized to overcome the pressure loss through the Rinnai water heater, supply and return plumbing. Refer - ence the Rinnai Hot Water System Design Manual, Pump Sizing for Circulation.

Pump to be of bronze or stainless construc - tion.

Note:

Water heater outlet temperature cannot be adjusted when circulation pump is running.

Minimum 3/4" Hot Water

Supply Line

Rinnai

Water Heater

Rinnai

 

Equipment List

QTY

Rinnai

1

Water Heaters

 

RIK-KIT (Optional)

1

 

(3/4" Fittings Include:

 

2

Unions, 2 Ball Valves,

 

2

Drain Valves and

 

1

Pressure Relief Valve.)

 

3 Years On Heat ExchangerManual background 3/4" Gas Connection

Gas Supply

Minimum 3/4" Cold Water Supply Line

(Optional)

2-6 Gallon Storage Tank

(To eliminate cold water sandwich effect caused by frequent On/Off operation)

Expansion Tank

Building Fixture Outlets

 

KEY

3/4" Ball Valve

Pressure Regulator

 

3/4" Union

Circulating Pump

Check Valve

Boiler Drain Valve

Pressure Relief Valve

S Solenoid Valve

This is not an engineered drawing, it is intended only as a guide and not as a replacement for professionally engineered project drawings. This drawing is not intended to describe a complete system, it is up to the contractor/engineer to determine the necessary components for and configuration of the particular system being installed. The drawing does not imply compliance with local building code requirements. It is the engineer/contractor responsiblity to ensure the installation is in accordance with all local building codes. Confer with local building officials before installation.