Clearances from Appliance
| to | to Non- | |
| Combustibles | Combustibles | |
|
|
| |
Top of | 12 inches | 2 inches | |
Heater | (305 mm) | (51 mm) | |
|
|
| |
Back of | 0 (zero) | 0 (zero) | |
Heater | |||
|
| ||
|
|
| |
Front | 24 inches | * 0 (zero) | |
(Panel) | (610mm) | ||
| |||
|
|
| |
Front | 24 inches | 24 inches | |
(Exhaust) | (610mm) | (610 mm) | |
|
|
| |
Sides of | 6 inches | 1/8 inches | |
Heater | (152 mm) | (3.2 mm) | |
|
|
| |
Floor/ | 12 inches | 2 inches | |
Ground | (305 mm) | (51 mm) | |
|
|
|
*The clearance for servicing is 24 inches in front of the water heater
to side
to floor/ground
to top
to front
Attachment of the Water Heater
1.Identify the installation location and confirm that the installation will meet all required clearances.
2.Securely attach the water heater to the wall using any of the holes in the wall installation brackets which are at the top and bottom of the water heater. Ensure that the attachment strength is sufficient to support the weight. Refer to the weight of the water heater in the Specifications section.
wall installation
brackets