Additional Clearances - Vent Terminal (RC80i, RC98i)
Local codes supersede these clearances.
•Avoid termination locations near a dryer vent.
•Avoid termination locations near commercial cooking exhaust.
•For air intake position, follow the ANS Z21.10.3, CSA 4.3 requirements on the previous page.
Vent terminal (represents concentric vent terminal or exhaust only vent terminal)
12"
(0.30 m ) to an inside corner
(0.91 m) to ventilated or unventilated soffit
36" or eve vent; or to a deck or porch
VV 12"
(0.30 m) between Rinnai terminals at same level
V
60" (1.52 m) vertically between Rinnai terminals
V
24" (0.61 m) to wall or parapet
V
INSIDE
CORNER
(1.52 m) between | 60" | |
Rinnai terminals | ||
| ||
at different levels | V |
V
12" |
| (0.30 m) between | |
V | V | Rinnai terminals at | |
same level | |||
|
|