Rinnai REU-VA3237FFU Flue Installation R98LSi, R98LSi-ASME, Air Intake Assembly

Models: REU-VA3237FFU

1 44
Download 44 pages 2.19 Kb
Page 32
Image 32
Flue Installation (R98LSi, R98LSi-ASME)

Flue Installation (R98LSi, R98LSi-ASME)

Air Intake Assembly

The air intake system consists of a field supplied 4 inch diameter stainless steel, Schedule 40 PVC, ABS or CPVC pipe. A maximum 6 feet of semi-rigid flexible aluminum ducting can also be used. Foil wrapped dryer vent and cell core products are not authorized.

The air intake has a zero clearance to combustibles.

Air Intake Connection

1.Drill 2 small holes at the end of the air intake pipe.

2.Slide the pipe over the air intake terminal.

3.Using a level, ensure the pipe is straight up and down.

4.With self tapping screws, attach the pipe to the air intake terminal.

5.Apply a bead of silicone around the pipe and air intake terminal, ensuring an air tight connection.

12

34

Exhaust Pipe Assembly

Refer to the manufacturerís installation instructions for the specific exhaust vent system.

Venting Clearances to Combustibles

Vent

Enclosed

Unenclosed

 

 

 

 

Size

Horizontal

Vertical

Horizontal

Vertical

 

 

 

 

 

 

4"(101.6mm)

4"(101.6mm)

4"(101.6mm)

1"(25.4mm)

1"(25.4mm)

 

 

 

 

 

Horizontal Terminations

The air intake must be located in relation to the exhaust as shown below. The air intake must angle 1/4 inch per foot to the termination to prevent entry of rain.

6

Vent

8

Optional

Intake

Intake

EXHAUSTAir Intake Assembly

COMBUSTION AIR / INTAKE 12

SLOPE INTAKE AND EXHAUST

TOWARD OUTSIDE TERMINATION

MINIMUM 1/4" PER FOOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

VA Series Indoor LS Manual

 

Page 32
Image 32
Rinnai REU-VA3237FFU installation manual Flue Installation R98LSi, R98LSi-ASME, Air Intake Assembly, Exhaust Pipe Assembly