Error Code Table

Code

Fault

 

Remedy

 

 

 

 

 

 

14

Thermal Fuse

 

Check gas type of unit and ensure it matches gas type being used.

 

 

 

 

Check for restrictions in air flow around unit and vent terminal.

 

 

 

 

Check for low water flow in a circulating system causing short-cycling.

 

 

 

 

Ensure dip switches are set to the proper position.

 

 

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

 

 

Check heat exchanger for cracks and/or separations.

 

 

 

 

Check heat exchanger surface for hot spots which indicate blockage due to scale build-up.

 

 

 

 

Refer to instructions in manual for flushing heat exchanger.

 

 

 

 

Measure resistance of safety circuit.

 

 

 

 

Ensure high fire and low fire manifold pressure is correct.

 

 

 

 

Check for improper conversion of product.

 

16

Over Temperature

 

Check for restrictions in air flow around unit and vent terminal.

 

 

Warning

 

Check for low water flow in a circulating system causing short-cycling.

 

 

 

 

Check for foreign materials in combustion chamber and/or exhaust piping.

 

 

 

 

Check for clogged heat exchanger.

 

31

Burner Sensor Error

 

Measure resistance of sensor.

 

 

 

 

Replace sensor.

 

32

Outgoing Water

 

Check sensor wiring for damage.

 

 

Temperature Sensor

 

Measure resistance of sensor.

 

 

Fault

 

Clean sensor of scale build-up.

 

 

 

 

Replace sensor.

 

33

Heat Exchanger

 

Check sensor wiring for damage.

 

 

Outgoing Temperature

 

Measure resistance of sensor.

 

 

Sensor Fault

 

Clean sensor of scale build-up.

 

 

 

 

Replace sensor.

 

34

Combustion Air

 

Check for restrictions in air flow around unit and vent terminal.

 

 

Temperature Sensor

 

Check sensor wiring for damage.

 

 

Fault

 

Measure resistance of sensor.

 

 

 

 

Clean sensor of scale build-up.

 

 

 

 

Ensure fan blade is tight on motor shaft and is in good condition.

 

 

 

 

Replace sensor.

 

52

Modulating Solenoid

 

Check modulating gas solenoid valve wiring harness for loose or damaged terminals.

 

 

Valve Signal Abnormal

 

Measure resistance of valve coil.

 

61

Combustion Fan Failure

 

Ensure fan will turn freely.

 

 

 

 

Check wiring harness to motor for damaged and/or loose connections.

 

 

 

 

Measure resistance of motor winding.

 

65

Water Flow Control Fault

 

The water flow control valve has failed to close during the bath fill function. Immediately turn

 

 

 

off the water and discontinue the bath fill function. Contact a state qualified or licensed

 

 

 

 

contractor to service the appliance.

 

71

Solenoid Valve Circuit

 

Replace the PC Board.

 

 

Fault

 

 

 

72

Flame Sensing Device

 

Ensure flame rod is touching flame when unit fires.

 

 

Fault

 

Check all wiring to flame rod for damage.

 

 

 

 

Remove flame rod and check for carbon build-up; clean with sand paper.

 

 

 

 

Check inside burner chamber for any foreign material blocking flame at flame rod.

 

 

 

 

Measure micro amp output of sensor circuit with flame present.

 

 

 

 

Replace flame rod.

 

73

Burner Sensor Circuit

 

Check sensor wiring and PC board for damage.

 

 

Error

 

Replace sensor.

 

LC

Scale Build-up in Heat

 

Flush heat exchanger. Refer to instructions in manual.

 

 

Exchanger (when

 

Replace heat exchanger.

 

 

checking maintenance

 

NOTE: The LC code is the only error code that will allow the unit to keep running. The

 

 

code history, “00” is

 

display will alternate between the LC code and the temperature setting. The controller will

 

 

substituted for “LC”)

 

continue to beep. The LC code will reset if power is turned off and then on.

 

No

Nothing happens when

 

Clean inlet water supply filter.

 

code

water flow is activated.

 

On new installations ensure hot and cold water lines are not reversed.

 

 

 

 

Check for bleed over. Isolate unit from building by turning off cold water line to building.

 

 

 

 

Isolate the circulating system if present. Open your pressure relief valve; if water is

 

 

 

 

flowing, there is bleed over in your plumbing.

 

 

 

 

Ensure you have at least the minimum flow rate required to fire unit.

 

 

 

 

Ensure turbine spins freely.

 

 

 

 

Measure the resistance of the water flow control sensor.

 

 

 

 

Check for DC shorts at components.

 

 

 

RV53i & RV53e Operation and Installation Manual

11