COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL
Burner Observation | Make sure it is clean and free of cracks or holes. |
Window | Clean and replace as required. |
| |
|
|
Flue Blower Scroll, Wheel | Compressed air or a vacuum cleaner may be used to clean dust and dirt. |
and Motor |
|
|
|
Inshot Burners and | Clear of obstructions (even spider webs will cause problems). |
Orifices | Carefully remove any dust and debris from the burner. |
| |
|
|
| Replace if there are cracked ceramics, excessive carbon residue, or erosion |
| of the electrode. |
| The electrode gap should be 1/8" (3.2 mm). |
|
|
Thermostat | There should be no exposed wire or damage to the device or wiring. |
| See Page 19, Section 10. |
|
|
Suspension Points | Make sure the heater is hanging securely. |
| Look for signs of wear on the suspension materials or ceiling. |
| See Page 6, Figure 2. |
|
|
Silicone Tubing | Ensure tight, secure fit on all pressure fittings at pressure switch, |
| burner partition, and blower outlet. |
|
|
Gas Valve | Verify that cap covering pressure regulator adjustment screw is secure and |
| has not been tampered with. |
| Verify all wiring connections. |
|
|
Condensate Drain | Flush drain and clear any obstructions. |
(when installed) |
|
|
|
26