Roberts Gorden 150, 200 SERVICING 12.1 Servicing Instructions, Burner Maintenance, Flue Blower

Models: 225 250 175 300 400 150 350 200

1 52
Download 52 pages 19.42 Kb
Page 30
Image 30
SECTION 12: SERVICING 12.1 Servicing Instructions

COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 12: SERVICING 12.1 Servicing Instructions

After start-up, the heater will require maintenance to be carried out annually. If the heater is used in a dirty or dusty area, more frequent maintenance may be necessary.

12.2 Burner Maintenance WARNING

Cut Hazard

Turn off gas and electrical supply before maintenance. Fan can start automatically at any time.

Failure to follow these instructions can result in severe injury or product damage.

NOTE 1: After any maintenance or repair work, always test fire the heater in accordance with the start-up instructions on Page 19, Section 10 through Page 21, Section 10.3.1 to ensure all safety systems are in working order before leaving the heater to operate. Minor faults may be traced by using the troubleshooting charts on Page 27, Section 13 through Page 30, Section 13.5.

NOTE 2: Check all gas pipes and pipe joints to ensure there are no cracks or gas leaks. Any cracks in the pipes or pipe joints must be repaired.

NOTE 3: Inspect all suspended components and hardware. Ensure that they are in good condition, properly tightened, and corrosion free.

12.2 Burner Maintenance

1.Open the door and remove the burner compart- ment cover. See Page 32, Section 14.2.

2.Clean any deposits from the main burner which may have formed in the injectors or venturi of the burner. See Page 32, Section 14.2.

3.Remove the ignition electrode and flame probe. Check condition of ignition electrode and flame probe. Clean off any deposits which may have been formed, check condition of ceramic insulators. Replace as necessary.

12.3 Fan/Motor Assembly Maintenance

The main fan bearings are permanently sealed and do not need lubrication. Before cleaning, turn off gas and electrical supply. Remove the fan and use a small brush or duster to clean the fan blades from each side. Replace fan when done.

12.4 Heat Exchanger Maintenance

The heat exchanger will remain clean unless a problem has developed with combustion. Inspect the heat exchanger. Look for signs of overheating at the front tubes which may indicate burner over firing or persistently low air flows.

12.5 Gas Valve Maintenance

No regular maintenance is required on this device. To change gas control valves, See Page 31, Section 14.1.

Do not repair or disassemble gas valve. Replace faulty gas valves with genuine replacement parts sold and supplied by Roberts-Gordon.

12.6 Flue Blower

The flue blower should not require maintenance. However, if the air pressure switch is causing burner lockout, then remove the flue blower from the vent box by unscrewing the three screws at the mounting plate. Remove the four screws attaching the mounting plate to the fan inlet (See Page 35, Section 14.6). Ensure that the fan is free to run and that the fan wheel is clean.

12.7 Venting and Air Intake Pipe

Inspect all venting and air intake pipe. Ensure that all seams are sealed and suspension points secure. Repair suspension points if any part of the venting or combustion air pipe is sagging. Check to make sure any insulation is not missing or in poor condition. Replace as necessary. Check all venting and air intake components to ensure they are in good condition, gas tight and corrosion-free.

24

Page 30
Image 30
Roberts Gorden 150, 200, 350 SERVICING 12.1 Servicing Instructions, Burner Maintenance, 12.3 Fan/Motor Assembly Maintenance