CGTH USE AND CARE MANUAL

 

Clearance to each

 

 

H

side of center line

3' (91 cm) within a height 15' (4.5 m) above

 

extended above

*

the meter/regulator assembly

 

meter/regulator

 

 

 

 

 

assembly

 

 

 

 

 

 

I

Clearance to

 

 

service regulator

3' (91 cm)

*

 

vent outlet

 

 

 

 

 

 

 

Clearance to non-

 

 

 

mechanical air

 

 

J

supply inletto

 

 

building or the

12" (30 cm)

9" (23 cm)

 

combustion air inlet

 

 

 

to any other

 

 

 

appliance

 

 

 

 

 

 

K

Clearance to

 

3' (91 cm) above if within 10' (3 m)

mechanical air sup-

6' (1.83 m)

horizontally

 

ply inlet

 

 

 

 

 

 

 

 

 

Clearance above

 

 

L

paved sidewalks or

 

 

paved driveway

7' (2.13 m)+

7’ (2.13 m)+

 

located on private

 

 

 

property

 

 

 

 

 

 

M

Clearance under

 

 

veranda, porch,

12' (30 cm)**

12" (30 cm)**

 

deck, or balcony

 

 

 

 

 

 

1In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code

2In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code

+A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings.

** Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1, one of the following shall be indicated:

a)A minimum clearance value determined by testing in accordance with section 4.7.3, 6.5.5, 8.5.5; or;

b)A reference to the following footnote:

"Clearance in accordance with local installation codes and the requirements of the gas supplier."