Samsung AP500PF Drilling a Hole in the Wall, Drain Hose, Rat-preventionCover, Installation Method

Models: AP500PF

1 34
Download 34 pages 24.25 Kb
Page 27
Image 27
INSTALLATION METHOD

INSTALLATION METHOD

Drilling a Hole in the Wall

Drill a hole of 70mm(3 inch) in diameter to the outside.

The drilling should be done at a distance of less than 150mm(6 inch) from the floor facing the indoor unit.

Drain Hose

Less than Drilling a Hole in the Wall ø70mm

150mm Drain HoseRat-prevention Cover (3 inch) (6 inch)

Extend the drain hose to the drain hose connected to the drain pan, and fix it with the tape or a cable tie to prevent separation. Then make a covering of it so that water can not flow outwardly.

Piping Material

Vinyl Chloride(Outer diameter ø 16mm/0.63 inch)

 

 

Insulator

Foamed Polyethylene

 

 

Drain pan

Band Manual background

Insulation

Drain hose Manual background

Indoor and outdoor connection

CAUTION

1.As the draining is of natural drain type, make the drain hose direct downward.

2.If there is any foreign substance in the drain plate, it may clog the drain pipe. Therefore, be sure to remove the foreign substance inside after installation.

3.After completion of installation, be sure to pour water into the drain pan,

and then check the draining condition.

(There is no problem in draining when the draining is completed within 20 seconds.)

Rat-prevention Cover Manual background

The piping of this unit can be connected to the left and rear side.

When you hit the area for piping connection slightly with a hammer, a hole is made. - If there is any reason to change connection, fill in hole with rubber cabi slot.

Holes for piping connection (2 points)

Rubber cabi slot

E-27

Page 27
Image 27
Samsung AP500PF installation manual Drilling a Hole in the Wall, Drain Hose, Rat-preventionCover, Installation Method