INSTALLING THE UNIT
Installing and Connecting the Indoor Unit Assembly Piping
B | A |
C | D |
There are two refrigerant pipes of different diameters:
◆A smaller one for the liquid refrigerant
◆A larger one for the gas refrigerant
A short length of piping is already fitted to the air conditioner. You must extend this piping using assembly piping (optionally supplied).
The connection procedure for the refrigerant piping varies according to the exit position of the piping from the indoor unit, as seen when facing the air conditioner in position on the wall:
◆Right (A)
◆Left (B)
◆Underside (C), (D)
◆Rear (C), (D)
1With a knife, cut out the appropriate
2Smooth the cut edges.
3Remove the protection caps on the pipes and connect the assembly piping to each pipe, tightening the nuts, first manually and then with a torque wrench, applying the following torque.
Outer Diameter | Torque (kgf•cm) |
6.35 mm | 140~170 |
9.52 mm | 250~280 |
12.70 mm | 380~420 |
➢If the piping must be shortened or extended, refer to page 11.
4Cut off any excess foam insulation.
5If necessary, bend the pipe round, along the bottom of the indoor unit and out through the appropriate hole, taking care to ensure that:
◆The piping does not jut out from the rear of the indoor unit
◆The bending radius is 100 mm or more
6Pass the piping through the hole in the wall.
7For further details on how to connect up to the outdoor unit and purge the circuit, refer to page 12.
➢The piping will be insulated and fixed permanently into position once the whole installation has been tested for gas leaks; refer to page 13 for further details.