Space Requirements for Outdoor UnitWhen installing 1 outdoor unit

Figure Description

 

Top view

 

Side view

 

Air intake

Air outlet

 

 

Air intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air outlet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

, Air flow direction.

When the air outlet is opposite the

When the air outlet is towards the

wall

wall

300 or more

1500 or more

ENGLISH

(Unit : mm)

When 3 sides of the outdoor unit are blocked by the wall

300 or more

150 or more

600 or more

The upper part of the outdoor unit and the air outlet is towards the wall

2000 or more

or more

 

1500

The upper part of the outdoor unit and the air outlet is opposite the wall

500 or more

 

 

 

 

 

 

 

 

 

 

 

 

300 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the walls are blocking front and the rear side of the outdoor unit

1500 or 300 or more more

When installing more than 1 outdoor unit

(Unit : mm)

When the air outlet is towards the wall

When 3 sides of the outdoor unit are blocked by the wall

or more

 

300 or more

1500

 

 

 

300 or more

600 or more 600 or more 600 or more

25